Field Settings for Outdoor Unit
Field Settings
118
2. Field Settings for Outdoor Unit
This section shows a list of field setting items possible to set at time of initial startup. For details of DIP switch
setting, setting mode ("mode 2") and monitoring mode ("mode 1"), refer to information on one after the following
page onwards.
2.1
Function Setting
Following settings may be required to set to comply to specific application requirements.
For detailed description about each setting, refer to “Description Field Settings (mode 2: m2) on Outdoor Unit
Main PCB” on page 145.
Note:
∗
1. ABC I/P PCB kit for
VRV
IV.
∗
2. External control adaptor for outdoor unit.
No
Setting item
Contents and objective of setting
Overview of setting procedure
1
Setting of COOL/
HEAT selection
To select cooling or heating mode by one
of the following methods:
1. From 1 indoor unit remote controller
(default).
2. From the optional COOL/HEAT switch.
Optional board “BRP2A81
∗
1” required
in outdoor unit.
3. Multiple outdoor systems from 1 indoor
unit remote controller.
4. Multiple outdoor systems from the
optional COOL/HEAT switch. Optional
board “BRP2A81” required in 1 outdoor
unit per zone.
2.1: Optional COOL/HEAT switch “KRC19-
26B”.
2.2: Set DIP switch DS1-1 on the outdoor
board to “OUT” (upper).
2.3: Install option “BRP2A81
∗
1” in outdoor
unit.
3.1: Set the system to “MASTER” or “SLAVE”
using mode 2-
0
.
3.2: Set COOL/HEAT zone address mode 2-
1
.
4: Combine 2 and 3.
2
Setting of low
noise operation
A. To reduce operation noise level through
reduction of the upper limit of the fan using
external input (use outdoor fan step 8 for
normal operation).
1. Level 1: upper than fan step 6.
2. Level 2: upper fan step 5 + upper limit
compressor capacity step mid level.
3. Level 3: upper fan step 5 + upper limit
compressor capacity step low level.
Use the optional board “DTA104A61
∗
2”.
Set “mode 2” No.
12-1
.
Choose level by “mode 2” No.
25
.
If required, set the “Capacity priority
setting” to “ON”, by “mode 2” No.
29-1.
B. To perform automatic night-time low noise
operation.
Start time: selectable from 20:00 to 24:00
hours (step by 2 hours).
End time: selectable from 06:00 to 08:00
hours (step by 1 hour).
(Note that the set time is estimated
according to outdoor air temperature.)
Select required level by mode 2-
22
.
Select start time with mode 2-
26
.
Select end time with mode 2-
27
.
Select capacity priority setting if required
by mode 2-
29-1
.
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...