5 Piping installation

Installation manual

12

4 35

35 3 RXTA30N2V1B

R32 split series

3P482320-10S – 2020.08

330

524

211

(mm)

211

a

a

100 mm above expected level of snow

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

INFORMATION

For  information  on  the  available  options,  contact  your
dealer.

5

Piping installation

5.1

Preparing refrigerant piping

5.1.1

Refrigerant piping requirements

Piping material:

 Phosphoric acid deoxidised seamless copper.

Piping diameter:

Liquid piping

Ø6.4 mm (1/4")

Gas piping

Ø9.5 mm (3/8")

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

5.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

5.1.3

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

20 m

Minimum allowable pipe length

1.5 m

Maximum allowable height difference

15 m

5.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking into account the following requirements:

ð

inside  occupied  spaces  non  permanent  joints  are  not
allowed for R32 refrigerant except for site made joints
directly connecting the indoor unit to piping. Site made
joints  directly  connecting  piping  to  indoor  units  shall
be of non permanent type.

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

Содержание RXTP25N2V1B8

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXTM30N2V1B RXTM40N2V1B RXTP25N2V1B9 RXTP35N2V1B9 RXTP25N2V1B8 RXTP35N2V1B8 ARXTP25N2V1B ARXTP35N2V1B RXTA30N2V1B...

Страница 2: ...j sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendament...

Страница 3: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Страница 4: ...ringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directive...

Страница 5: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Страница 6: ...isina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele res...

Страница 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Страница 8: ...6 12 1 Wiring diagram 17 12 1 1 Unified wiring diagram legend 17 12 2 Piping diagram 18 12 2 1 Piping diagram Outdoor unit 18 1 About the documentation 1 1 About this document INFORMATION Make sure th...

Страница 9: ...iping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abnormal pressure in...

Страница 10: ...SK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST...

Страница 11: ...el is less than 70 dBA The outdoor unit is designed for outdoor installation only and for ambient temperatures within the following ranges Cooling mode Heating mode 10 46 C DB 25 24 C DB 4 1 2 Additio...

Страница 12: ...C Insulation thickness Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is higher than 30 C and the hu...

Страница 13: ...n the brass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect...

Страница 14: ...harge the additional refrigerant amount 3 Open the gas stop valve 6 5 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated greenhouse gases 2 1 1 1 2 2 k...

Страница 15: ...verload relay lead wire h DB1 diode bridge 7 1 Specifications of standard wiring components Component Power supply cable Voltage 220 240 V Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 a b 4...

Страница 16: ...pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open The following fie...

Страница 17: ...LED V L Pilot lamp light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic r...

Страница 18: ...4 CuT 6 4 CuT 9 5 CuT 7 9 CuT 9 5 CuT 9 5 CuT 12 7 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6x7 0 CuT HPS 6 4 CuT k 12 7 CuT 6x3 2 CuT 6 4 CuT f h i j e a Field piping liquid b Field piping gas c Liquid stop valv...

Страница 19: ......

Страница 20: ...3P482320 10S 2020 08 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: