
SiUS331708EA
Troubleshooting by Error Code
Service Diagnosis
154
4.2
Error Codes - Sub Codes
If an error code like the one shown below is displayed when the navigation remote controller (BRC1E series) is in
use, make a detailed diagnosis or a diagnosis of the relevant unit.
4.2.1 Indoor Unit
Error code
Troubleshooting
Description of error
Description of diagnosis
A0 - 01
External protection device abnormality
Refer to page 161.
A6 - 01
Fan motor locked
A locked fan motor current has been detected.
Turn the fan by hand to check for the connection of connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected.
Check for the connection of the connector between the fan motor
and the fan PCB. If the connection is normal, replace the fan
motor. If this still cannot solve the error, replace the fan PCB.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check for the
connection of the connector between the fan motor and the fan
PCB. If the connection is normal, replace the fan motor. If this still
cannot solve the error, replace the fan PCB.
A6 - 20
Indoor fan motor status abnormality
Refer to page 173.
A6 - 21
Low indoor airflow
Refer to page 174.
A8 - 01
Power supply voltage error
Check for the input voltage of the fan motor.
A9 - 01
Electronic expansion valve error
There is an error in the electronic expansion valve coil or a
connector disconnected.
A9 - 02
Refrigerant leakage detection error
Refrigerant leaks even if the electronic expansion valve is closed.
Replace the electronic expansion valve.
AA - 03
Gas furnace abnormality
Refer to page 180.
AH - 03
Transmission error (between the self-cleaning
decoration panel and the indoor unit)
(when the self-cleaning decoration panel is
mounted)
Check for the connection of the harness connector between the
panel PCB and the indoor unit PCB.
AH - 04
Dust detection sensor error
(when the self-cleaning decoration panel is
mounted)
Check for the connections of the connector X12A on the panel
PCB and the connectors X18A and X19A on the sensor PCB.
AH - 05
Dust collection sign error
(when the self-cleaning decoration panel is
mounted)
Check for clogging with dust at the dust collection port as well as
in the brush unit, S-shaped pipe, and dust box. Furthermore,
check for any stains of the light receiving and emitting parts of the
infrared unit.
AH - 06
Air filter rotation error
(when the self-cleaning decoration panel is
mounted)
Check for anything getting in the way of rotating the filter (e.g. the
filter comes off or the drive gear is clogged with foreign matter).
AH - 07
Damper rotation error
(when the self-cleaning decoration panel is
mounted)
The damper does not rotate normally. Check for any foreign
matter around the damper and for the operation of the gear and
limit switch.
AH - 08
Filter self-cleaning operation error
(when the self-cleaning decoration panel is
mounted)
The unit has not yet completed the filter self-cleaning operation
even after the lapse of specified period of time. Check for any
external noise, etc.
AH - 09
Filter self-cleaning operation start disabled error
(when the self-cleaning decoration panel is
mounted)
The unit has been put into a state in which the filter self-cleaning
operation is disabled. Check the unit for the operating conditions.
AJ - 01
Capacity setting error
There is an error in the capacity setting of the indoor unit PCB.
AJ - 02
Electronic expansion valve setting error
There is a fault in the setting of the gear type electronic expansion
valve/direct acting type electronic expansion valve.
C1 - 01
Transmission abnormality between indoor unit
PCB and fan PCB
Check for the conditions of transmission between the indoor unit
PCB and the fan PCB.
C1 - 07
Blower motor communication error
Refer to page 185.
C1 - 08
Climate Talk Communication error
Refer to page 186.
C6 - 01
Defective combination of indoor unit PCB and
the fan PCB
A combination of indoor unit PCB and the fan PCB is defective.
Check whether the capacity setting adaptor is correct and the
type of the fan PCB is correct.
Blower motor HP mismatch
Refer to page 189.
C6 - 02
Indoor blower does not have required
parameters to function
Refer to page 190.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...