Symptom-Based Troubleshooting
SiUS331708EA
147
Service Diagnosis
2.2
With Optional Infrared Presence/Floor Sensor
Error diagnosis of "Louver operation different from setting"
Condition
Measure
1
"Louver operation different from setting" or "No downward
airflow in heating operation"
Refer to the following table.
2
Individual airflow direction setting different from the actual
airflow direction
· Check the "Louver operation different from setting" error
diagnosis.
3
When in stop mode, the louver does not close completely.
Turn off the circuit breaker and then turn it on again.
4
The remote controller menu does not display energy saving
operating mode for when people are not present.
Please check "Infrared presence/floor sensor error (CE)" in
troubleshooting.
The remote controller menu does not display the stop
function for when people are not present.
The remote controller menu does not display the automatic
draft prevention function.
5
The menu does not display the eco-friendly display function.
No defect.
Set the clock.
6
During cooling and dry operation, the louver automatically
switches from horizontal (P0) to one-level downward (P1).
No defect.
When relative ambient humidity is higher, automatic louver
control will be activated.
7
During heating operation, the use of an airflow block will not
cause other louvers to turn downward (P4).
No defect.
In heating operation, if an airflow block is set, then the air
outlet control outside the airflow block will be within the
range P0-P3.
8
When using airflow block, the airflow block will be routinely
lifted (become horizontal) during heating operation.
No defect.
Set louver to horizontal (P0) during thermostat OFF.
9
Although people are not present, the infrared presence
sensor detects human presence.
Check if there are any objects that generate temperature
change when moving.
For example:
· An electric heater with swing function
· Doors, curtains, blind switches
· Output of paper from a fax machine or a printer
· Turning on/off of incandescent lights
· Moving objects
10
Although people are present, the infrared presence sensor
fails to determine their presence.
Check for the following conditions.
· Lack of movement
· Facing away from the sensor
· Little skin exposed
· Slight movement in a place far from the sensor
11
Large difference between floor temperature and actual
temperature
Check for the following conditions.
· Sensor detection zone affected by solar radiation
· High or low temperature objects in the sensor detection zone
· Large difference between floor temperature and
temperature of the living space
· Sensors installed near walls may be affected by wall temperature.
Normal
Reset (Cancel)
individual airflow.
Is the individual
airflow set?
Is the
airflow direction set to
automatic?
Is the
wire harness
broken?
YES
YES
NO
NO
NO
NO
NO
Replace the step
motor. (Motor failure)
YES
Replace the wire
harness.
YES
Is the connection
of the step motor
connector normal?
Is the
automatic draft prevention
function "enabled"?
YES
Normal
Automatic draft
prevention function
switches flap to
horizontal position
when human
presence is detected.
Connect to the
connector
correctly before
action verification.
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...