SiUS331708EA
Field Settings from Outdoor Unit
Field Settings and Test Operation
126
2.7
Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective electronic expansion valve of indoor
and outdoor units.
All indoor and outdoor unit’s operation are prohibited.
Operation procedure
(1) In setting mode 2 with units in stop mode, set the item 2-21 (refrigerant recovery / vacuuming mode) to ON.
The respective expansion valve of indoor and outdoor units are fully opened.
Test Operation
and
Under
Centralized Control
are displayed on the remote controller, and the indoor / outdoor unit operation is
prohibited.
After setting, do not cancel setting mode 2 until completion of refrigerant recovery operation.
(2) Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the refrigerant
recovery unit for more detail.)
(3) Press the
MODE (BS1)
button once and return to setting mode 2.
2.8
Setting of Vacuuming Mode
In order to perform vacuuming operation on site, fully open the electronic expansion valves of indoor and outdoor
units and turn on some solenoid valves.
Operating procedure
(1) In setting mode 2 with units in stop mode, set the item 2-21 (refrigerant recovery / vacuuming mode) to ON.
The respective expansion valve of indoor and outdoor units are fully opened.
Test Operation
and
Under
Centralized Control
are displayed on the remote controller, and the indoor / outdoor unit operation is
prohibited.
After setting, do not cancel setting mode 2 until completion of Vacuuming operation.
(2) Use the vacuum pump to perform vacuuming operation.
(3) Press the
MODE (BS1)
button once and reset setting mode 2.
2.9
Final Charge Adjustment
The following operation is needed only when the most adequate refrigerant charge for the best performance is
required and the piping length between the outdoor and indoor units is less than 15 m (50 ft). Besides the
conditions above, this final adjustment is unnecessary.
Procedure
(1) While in setting mode 2, set the item 2-20 (Additional refrigerant charge operation setting) to ON. (LEDs:
kh
)
(2) While in setting mode 2, set the item 2-7 (SC adjustment) to ON. (LEDs:
kh
)
(3) Cooling operation begins; wait until the compressor achieves charge mode rotation speed.
Charge mode rotation speed achieved:
(LEDs:
kkhhhhk
)
Charge mode rotation speed not yet achieved:
(LEDs:
kkhhhhh
)
(4) Charge the refrigerant through the liquid stop valve charge port.
(5) Measure the liquid stop valve temperature. Charging is complete when the temperature reaches the target
subcooling.
Target subcooling
24 class
3.33 ± 0.56°C (6 ± 1°F)
36 class
1.11 ± 0.56°C (2 ± 1°F)
48 class
6.67 ± 0.56°C (12 ± 1°F)
60 class
7.78 ± 0.56°C (14 ± 1°F)
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...