Field Settings from Remote Controller
SiUS331708EA
101
Field Settings and Test Operation
Compensating the Floor Temperature
(For units with the infrared presence/floor sensor only)
Offset the detected value of the infrared floor sensor with a certain temperature. This setting should be used to
have the actual floor temperature detected when, for example, the unit is installed close to a wall.
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed in the following
cases:
Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is output
between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input is performed
from the T1-T2 terminal of the operation terminal block in the electrical component box.
Mode No.
First Code No.
Second Code No.
Contents
11 (21)
9
01
–4°C (–7.2°F)
02
–2°C (–3.6°F)
03
0°C (0°F)
04
+2°C (+3.6°F)
Environment
Operation Mode
Problem
Setting Value
· The unit is installed close to a wall or a window.
· High thermal capacity of the floor (such as
concrete, etc).
· There are many heat sources including PC.
· There is a non-negligible heat source such as
floor heating.
Heating
Excessive heating
+2°C (+3.6°F)
Insufficient heating
–2°C or –4°C
(–3.6°F or –7.2°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with "Start/Stop" of remote controller is
provided.
04
In case of "Error Display" appears on the remote
controller, output is provided.
05
—
06
—
07
Only for FXMQ-PB
Economizer (field supply) ON/OFF signal is provided.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates
A0
. The other indoor units indicate
U9
.
04
—
05
Only for FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
F2 T1 T2
Forced stop
Input A
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...