INSTALLATION 

MANUAL

R410A Split Series

Models
RXS30LVJU
RXS36LVJU
RKS30LVJU
RKS36LVJU

00_CV_3P300674-3.indd   1

10/21/2011   1:32:11 PM

Содержание RXS30LVJU

Страница 1: ...it series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS30LVJU RXS36LVJU RKS30LVJU RKS36LVJU 00_CV_3P...

Страница 2: ...s so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk o...

Страница 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Страница 4: ...ything under the unit which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be...

Страница 5: ...e below the ceiling surface 9 7 8 250 from wall Allow space for piping and electrical servicing Right side plate 13 3 4 350 Clamping material Insulation tube Bottom frame Tape Also insulate the connec...

Страница 6: ...ain socket A drain caps B and a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance 1 Insert drain receiver C onto drain socket A and drain cap B beyond 4 p...

Страница 7: ...flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 3 8 inch 9 5mm 24 1 29 4ft lbf 32 7 39 9N m Gas side 5 8 inch 15 9mm 45 6 55 6ft lbf 61 8 75 4N...

Страница 8: ...e gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swi...

Страница 9: ...as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylen...

Страница 10: ...cooling operation switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally pu...

Страница 11: ...ng the binding band as shown in the gure Secure rmly making sure no outside pressure is exerted on the terminals Power supply terminal block L1 L2 1 2 3 Use the speci ed wires and connect them securel...

Страница 12: ...s designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 You can expand the operation range to 14 F 10 C by turning...

Страница 13: ...Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of po...

Страница 14: ...3P300674 3 M11B136 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 3 indd 2 10 21 2011 1 32 12 PM...