6.3 Superheat Operation Check
CHECK 3
Identify the defective points referring to the failure factor analysis (FTA) as follows.
1. “Superheating temperature control” in cooling mode is conducted by indoor unit electronic
expansion valve.
2. Judgment criteria of superheat operation:
(1) Suction gas superheating temperature: 10 degrees and over.
(2) Discharge gas superheating temperature: 45 degrees and over, except for immediately after
starting and dropping control, etc.
(Use the above stated values as a guide. Depending on the other conditions, the unit may be
normal despite the values within the above scope.)
CHECK 7
Refer to page 293.
CHECK 8
Refer to page 294.
Temperature
increase of
discharge
pipe
Defective
discharge
pipe
temperature
control
Compressor
overheat
Defective
superheated
degree
control.
Refrigerant
shortage
Large resistance
of piping
Defective hot
gas bypass
control
Defective
subcooling
electronic
expansion valve
control (Y2E)
Superheat due to
shaft damage
Superheat due to
defective compressor
Indoor unit
electronic
expansion
valve failure
Irregular piping length
Bend/collapse
(Including moisture choke)
Stop valve is closed.
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective outdoor unit main PCB
Subcooling
electronic
expansion
valve failure
Control
failure
Defective valve coil
Defective valve
body
Defective low
pressure sensor
Defective subcooling
heat exchanger outlet
thermistor
Defective outdoor
unit main PCB
Defective valve coil
Defective valve body
Check if coil resistance and insulation
are normal.
Check if coil resistance and
insulation are normal.
Check if the voltage property is
normal.
Check if the connector is connected properly.
Check if the thermistor resistance property is
normal.
Check if the pressure value given by the
service checker corresponding to actual
measurement value by the sensor.
Check if coil resistance and insulation are
normal.
Does the piping length fall in the permissible range?
Conduct visual checks.
Remove the moisture by vacuum break. (Refer to
CHECK 8
)
Check if the stop valve is open.
If the indoor unit
electronic
expansion valve is
excessively
throttled. (
1)
Refer to
CHECK 7
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...