SiAF341904E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
95
8.3 Automatic Airflow Rate Control
The automatic airflow rate control (Five steps from H to L) is based on the difference between
control target temperature and set temperature.
1. LL airflow for FXFSQ
Conditions
When airflow
rate is set
Automatic airflow rate
Cooling
Thermostat ON
Set
The fan tap is determined
by the difference between
control target
temperature
and set temperature.
Thermostat OFF
Set (
1)
The fan keeps rotating at
the speed as just before
the thermostat off (
1)
Program dry
Thermostat ON
L
L
Thermostat OFF
OFF
OFF
Fan
Set
M
Stop
OFF
OFF
H
HM
M
ML
L
Fan tap
Large
Difference between control target
Small
temperature and set temperature
<Change in airflow rate under
automatic airflow rate control>
Except for FXFSQ,
HM and ML taps appear
only during the auto
airflow rate control
operation.
(For FXFSQ, HM and
ML taps can be
manually set with
remote controller.)
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...