Electrical installation
Installer reference guide
51
RXF50~71D5V1B
R32 split series
4P519439-18T – 2022.06
Component
Earth leakage circuit breaker
MUST comply with applicable legislation
(a)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and ≤75 A per phase).
9.2 To connect the electrical wiring to the outdoor unit
1
Remove the service cover. See
"6.2.2 To open the outdoor unit"
2
Remove the switch box cover.
2×
2
1
1
3
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
4
Open the wire clamp.
5
Connect the interconnection cable and power supply as follows:
f
50 Hz
220-240 V
a
b
c
d
e
a
Interconnection cable
b
Power supply cable
c
Circuit breaker
d
Residual current device
e
Power supply
f
Earth