
7
|
Piping installation
Installer reference guide
35
RXM-A, ARXM-A
R32 split series
4P718129-3A – 2023.07
7.2.1 About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪
Connecting the refrigerant piping to the indoor unit
▪
Connecting the refrigerant piping to the outdoor unit
▪
Insulating the refrigerant piping
▪
Keeping in mind the guidelines for:
-
Pipe bending
-
Flaring pipe ends
-
Using the stop valves
7.2.2 Precautions when connecting the refrigerant piping
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety precautions"
▪
"7.1 Preparing refrigerant piping"
DANGER: RISK OF BURNING/SCALDING
NOTICE
▪
Use the flare nut fixed to the unit.
▪
To prevent gas leakage, apply refrigeration oil ONLY to the inside of the flare. Use
refrigeration oil for R32 (FW68DA).
▪
Do NOT reuse joints.
NOTICE
▪
Do NOT use mineral oil on flared part.
▪
Do NOT reuse piping from previous installations.
▪
NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.