6
|
Unit installation
Installer reference guide
27
RXM-A, ARXM-A
R32 split series
4P718129-3A – 2023.07
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only and for ambient
temperatures specified in the table below (unless otherwise specified in the
operation manual of the connected indoor unit).
Cooling
Heating
–10~50°C DB
–20~24°C DB
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
b
c
a
Snow cover or shed
b
Prevailing wind direction
c
Air outlet
It is recommended to provide at least 150 mm of free space below the unit
(300 mm for heavy snowfall areas). Additionally, make sure the unit is positioned at
least 100 mm above the maximum expected level of snow See
28] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed.