Check
Service Diagnosis
100
5.12 Main Circuit Short Check
Check No.20
Note:
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is
approximately 0 V before checking.
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is
∞
or less than 1 kW, short circuit occurs on the main circuit.
20/25/35 class
50 class
Negative (–) terminal of multimeter
(positive terminal (+) for digital
multimeter)
~
(2, 3)
+
(4)
~
(2, 3)
–
(1)
Positive (+) terminal of multimeter
(negative terminal (–) for digital
multimeter)
+
(4)
~
(2, 3)
–
(1)
~
(2, 3)
Resistance is OK.
several k
Ω
~ several M
Ω
∞
∞
several k
Ω
~ several M
Ω
Resistance is NG.
0
Ω
or
∞
0
0
0
Ω
or
∞
(R19933)
1
2
3
4
Multimeter
–~
~
+
–
+
Multimeter
–
~
~
+
1
2
3
4
– +
(R19943)