
7
|
Piping installation
Installer reference guide
41
RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
▪
After handling the stop valve, tighten the stem cap, and check for refrigerant
leaks.
Piping Ø (mm)
Width across flats
Tightening torque
(N∙m)
6.4
17 mm
15~17
9.5
19 mm
18~20
12.7
22 mm
21~28
15.9
27 mm
48~59
To handle the service cap
▪
ALWAYS use a charge hose equipped with a valve depressor pin, since the service
port is a Schrader type valve.
▪
After handling the service port, tighten the service port cap, and check for
refrigerant leaks.
Item
Tightening torque (N∙m)
Service port cap
11~14
7.2.7 To connect the refrigerant piping to the outdoor unit
▪
Piping length.
Keep field piping as short as possible.
▪
Piping protection.
Protect the field piping against physical damage.
1
Connect the liquid refrigerant connection from the indoor unit to the liquid
stop valve of the outdoor unit.
a
b
c
a
Liquid stop valve
b
Gas stop valve
c
Service port
2
Connect the gas refrigerant connection from the indoor unit to the gas stop
valve of the outdoor unit.
NOTICE
It is recommended that the refrigerant piping between indoor and outdoor unit is
installed in a ducting or the refrigerant piping is wrapped with finishing tape.
7.3 Checking the refrigerant piping
7.3.1 About checking the refrigerant piping
The outdoor unit's
internal
refrigerant piping has been factory tested for leaks. You
only have to check the outdoor unit's
external
refrigerant piping.
Содержание RXF50D5V1B
Страница 1: ...Installer reference guide R32 split series RXF50D5V1B RXF60D5V1B RXF71D5V1B ...
Страница 22: ...4 About the box Installer reference guide 22 RXF50 71D5V1B R32 split series 4P519439 15Q 2021 10 1 2 ...
Страница 73: ......
Страница 74: ......
Страница 75: ......