background image

4 Installation

Installation manual

5

RXA20~35A2V1B
R32 split series
3P517827-1 – 2017.12

3.2

Preparing refrigerant piping

3.2.1

Refrigerant piping requirements

Piping material:

 Phosphoric acid deoxidised seamless copper.

Piping diameter:

Liquid piping

Ø6.4 mm (1/4")

Gas piping

Ø9.5 mm (3/8")

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

3.2.2

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

20 m

Minimum allowable pipe length

1.5 m

Maximum allowable height difference

15 m

3.2.3

Refrigerant piping insulation

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

4

Installation

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

311

574

211

(mm)

211

>300

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  In  this  case,  it  is
recommended to construct a pedestal.

311

574

211

211

(mm)

>300

100

a

a

Maximum snowfall height

If  the  unit  is  installed  on  brackets  to  the  wall,  install  the  unit  as
follows:

Содержание RXA20A2V1B

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXA20A2V1B RXA25A2V1B RXA35A2V1B...

Страница 2: ...s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standa...

Страница 3: ...klist before commissioning 10 5 2 Checklist during commissioning 10 5 3 To perform a test run 10 6 Configuration 10 6 1 To set the facility mode 10 7 Troubleshooting 11 7 1 Fault diagnosis using LED o...

Страница 4: ...he air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so...

Страница 5: ...fference 15 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is...

Страница 6: ...outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field su...

Страница 7: ...with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solut...

Страница 8: ...4 4 3 To determine the additional refrigerant amount If the total liquid piping length is Then 10 m Do NOT add additional refrigerant If the total liquid piping length is Then 10 m R total length m o...

Страница 9: ...ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DC DC g h b c d e f a a Multimeter DC voltage range b S70 fan motor lead wire...

Страница 10: ...etween the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The s...

Страница 11: ...r before removing the refrigerant piping If the compressor is still running and the stop valve is open during pump down air will be sucked into the system Compressor breakdown or damage to the system...

Страница 12: ...N E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...3P517827 1 2017 12 Copyright 2017 Daikin...

Отзывы: