Troubleshooting for FTXR Series
Part 6 Service Diagnosis
129
5.3 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code
A6
Method of Error
Detection
The rotation speed detected by the Hall IC during indoor fan motor operation determines abnormal
fan motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and is
less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
Содержание RX-W Series
Страница 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Страница 15: ...SiUS092230EA Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 107: ...SiUS092230EA BRC082A41W BRC082A42W S Part 5 Remote Controller 101 4 BRC082A41W BRC082A42W S R23936 R23937 ...
Страница 151: ...SiUS092230EA Troubleshooting for FDMQ FFQ Series Part 6 Service Diagnosis 145 Reference Check No 02 Refer to P 191 ...
Страница 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 238: ...Piping Diagrams SiUS092230EA 232 Part 8 Appendix 1 2 Outdoor Unit RX09 12WMVJU9 RX15 18WMVJU9 3D135014 3D141501 ...
Страница 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...
Страница 246: ...Operation Limit SiUS092230EA 240 Part 8 Appendix 3 Operation Limit RX09 12 15 18 24WMVJU9 3D092209F ...