Post-running CH
After the end of the CH-operation, the pump will run for a specified time. The post-pumping
time is set to the value in par. 7.2 in its factory settings. This setting can be changed. In
addition to this, the pump will run automatically 1 time per 24 hours, for 10 seconds, in order
to prevent it from getting stuck. This automatic switching on of the pump takes place at the
time of the last heating request. In order to change this, the room thermostat needs to be set
higher for a moment, at the required time of day.
1
Requested temperature reached
The boiler controller may temporarily block the heat request. The boiler controller will
then be stopped. The block occurs because the required temperature has been
reached. When the temperature has sufficiently decreased, the block will be lifted.
2
Selftest
Once every 24 hours, the boiler controller tests the connected sensors. During the test,
the relay will not carry out any other tasks.
3
Ventilating
When the unit is started, the fan is first brought up to its correct start rpm. When the
start rpm is reached, the boiler controller will be ignited. Code
3
is also visible when
there is post-fanning after the boiler controller is stopped.
4
Igniting
When the fan has reached the start rpm, the burner relay will be ignited by means of
electrical sparks. During the ignition, code
4
is displayed. If the boiler controller does
not ignite, a new attempt will be made after approximately 15 seconds. If after 4 ignition
attempts, the boiler controller has still not been ignited, the controller will go into down-
time.
5
CH operation
An on/off thermostat, an OpenTherm thermostat, an outdoor sensor or a combination
thereof can be connected to the controller (see par. 10.3)
When there is a heat request from a thermostat, after the fan has started running (code
3
), the ignition will take place (code
4
) followed by the CH operating mode (code
5
).
During CH operation, the rpm of the fan and therefore the power of the unit can be
adjusted so the temperature of the CH water to the required CH supply temperature can
be controlled. If an on/off thermostat has been connected, this will be the CH supply
temperature set on the display. In case of an OpenTherm thermostat, the required CH
supply temperature is determined by the thermostat. In case of an outdoor sensor, the
required CH supply temperature is determined by the fuel line programmed in the boiler
controller. For the last two situations, the temperature set on the display is the
maximum.
During CH operation, the requested CH supply temperature will be displayed on the
operating panel.
The CH supply temperature can be set between 30 and 90°C (see par. 7.1). Caution:
for a low temperature system, a lower maximum setting may be required than the
standard setting of 80°C.
You can press the service button during CH operation to read the actual CH supply
temperature.
If the tap comfort function is switched on (see code
7
), an OpenTherm heatingrequest
of less than 40 degrees will be generated.
Содержание Rotex GW-30 H12
Страница 1: ...ROTEX 4P381271 88527701 02 2016 4P381271 88527701 02 2016...
Страница 29: ...30...
Страница 80: ...30...
Страница 132: ...31...
Страница 184: ...31...
Страница 236: ...31...
Страница 287: ...ROTEX Heating Systems GmbH 30...
Страница 339: ...30...
Страница 392: ...31...
Страница 416: ...ROTEX 008 1548899_00 88527703 05 2018...