Mechanical Installation
www.DaikinApplied.com 39
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Table 11:
Approximate R-22 Refrigerant Charge Per Circuit, 015C - 040C
Unit size
Base charge lbs . per circuit (less DX coil)
EVAP .coil (lbs/CKT/
coil row)
Additional charge for heat section
additional length
Condenser
pumpdown
capacity* (lbs)
Circuit #1
Circuit #2
Circuit #1
Circuit #2
015 to 018
11
18
0.8/1.5
0.5
1
47
020C
11
18
0.8/1.5
1
1
47
025C
23
22
1.7
1
1
72
030C
23
21
1.7
1
1
72
036C
32
32
1.7
1
1
106
040C
33
32
1.7
1
1
106
* Condenser pumpdown capacity is the total charge for both circuits and is based on volume between condenser entrance and liquid linesolenoid at 90°F, 90% full
Table 12: Approximate R-22 Refrigerant Charge Per Circuit, 045C - 105C
Unit size
Base charge lbs . per circuit (less DX coil)
DX coil charge lbs per circuit per coil row
Condenser
pumpdown
capacity** (lbs)
RPS
RDT
DX=S*
DX=L*
Circuit #1
Circuit #2
Circuit #1
Circuit #2
045C
34
33
34
28
2.5
—
108
050C
34
33
35
34
2.5
3.0
108
060C
35
34
35
34
2.5
3.0
108
070C
39
39
40
40
2.5
3.0
134
075C
39
39
40
40
2.5
3.0
134
080C
40
41
37
38
4.1
4.7
140
090C
46
47
44
47
4.1
4.7
160
105C
50
51
45
48
4.9
6.5
208
* DX coil configuration (S = Standard, L = Large) is identified by the eighth digit of the RPS/RDT or RFS model number, found on the unit nameplate.
For example, DX = L for unit model number RFSO6OCLY.
** Condenser pumpdown capacity is the total charge for both circuits and is based on volume between condenser entrance and liquid linesolenoid at 90ºF, 90% full.
Table 13: Approximate R-407C Refrigerant Charge Per Circuit, 015C - 040C
Unit size
Base charge lbs . per circuit (less DX coil) Evaporator coil (lbs/
CKT/coil row)
Additional charge for heat section
additional length
Condenser
pumpdown
capacity* (lbs)
Circuit 1
Circuit 2
Circuit 1
Circuit 2
015C to 018C
10
16
0.7/1.4
0.5
1
45
020C
10
16
0.7/1.4
1
1
45
025C
21
20
1.6
1
1
68
030C
21
19
1.6
1
1
68
036C
29
29
1.6
1
1
101
040C
30
29
1.6
1
1
101
* Condenser pumpdown capacity is the total charge for both circuits and is based on volume between condenser entrance and liquid linesolenoid at 90°F, 90% full