7
Parameter settings
Operating Instructions
36
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
AUX switching
function
Setting assigns the switching conditions for the potential-free AUX switch-
ing contact (toggle switch output A, see
).
-
N
E
Inactive
Function deactivated.
AUX switching contact switches:
Switching
threshold TDHW
(AUX)
If storage tank temperature (Tdhw) ≥ value of [Switching threshold TDHW
(AUX)] parameter.
Heating/cooling
request
If a cooling request or heating request is present.
BUH request
If a hot water request to the backup heater (EKBUxx) is present or the con-
figured backup heater is requested for heating support.
Error
If an error is pending
TVBH > 60 °C If the sensor value (TVBH) is > 60 °C.
Outside temper-
ature
If the outside temperature is < [Bivalence temperature] parameter value.
(heat pump continues to operate = parallel equilibrium mode)
Outside temp. +
DHW/heating
If the outside temperature is < [Bivalence temperature] parameter value +
a heating request or a hot water request is present. (heat pump does not
continue to operate = alternative equilibrium mode)
DHW request
If a hot water request is present.
Outside temper-
ature + heating
If the outside temperature is < [Bivalence temperature] parameter value +
"room heating" heat request (not for hot water request). Heat pump no
longer operates in room heating mode below the value set in the [Bi-
valence temperature] parameter – only in hot water mode.
Application: Alternative room heating bi-valence mode if the boiler is hy-
draulically integrated so that it directly heats the unpressurised storage
tank water of the Daikin Altherma ETS(X/H) (connection via solar connec-
tions).
Multi-oil
If the outside temperature is < [Bivalence temperature] parameter value +
"room heating" heat request (not for hot water request). Heat pump no
longer operates in room heating mode below the value set in the [Bi-
valence temperature] parameter – only in hot water mode.
Application: Alternative room heating equilibrium mode if the boiler is hy-
draulically integrated in the heat pump feed. For this application type, the
frost protection function must be deactivated on the Daikin Altherma
ETS(X/H) ([Frost protection temperature] parameter = Off).
Cooling mode
If the heat pump is in the "Cooling" operating mode.
AUX wait time
0 – 600 s
AUX switching contact (A) only switches after a delay if the switching con-
dition (see [AUX switching function] parameter) is present for longer than
the set time.
120 s
5 s
N
E
Switching
threshold
TDHW (AUX)
20 – 85 °C
Storage tank temperature (Tdhw) switching threshold for AUX switching
contact (see [AUX switching function] parameter).
50 °C
1 °C
N
E
Tab. 7-11
Parameter in the "Inputs/Outputs" menu
7.5.5
Menu: Intelligent Storage Mgmt
[→ Main menu → Settings → ISM]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Continuous
heating
This function enables uninterrupted heating, even when the evaporator is
being defrosted. This enables high comfort to be guaranteed, even with
rapidly reacting heating systems (e.g. convectors).
-
N
E
Off
No uninterrupted heating
On
Uninterrupted heating. When the evaporator is being defrosted, heat for
heating is taken from the storage tank.
Heating sup-
port (HZU)
Heating support from hot water storage tank if minimum temperature is ex-
ceeded (see
and [Heating support hysteresis] parameter).
-
N
E
Off
No heating support
On
Heating support function active
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...