Protection Control
SiUS181305E
53
Function
4.4
Inverter Protection Control
Outline
Inverter overcurrent protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, temporary inverter overcurrent, or radiation fin temperature increase.
<Inverter overcurrent protection control>
<Inverter fin temperature control>
Not limited
Limited
Inverter current > 23.8 A
Inverter current > 23.8 A
Inverter current
≥
24.9 A continues for 260 sec.
&
&
Inverter current
standby
Inverter current
≤
23.8 A
continues for 3 min.
Without conditions
(R15610)
When occurring 4 times within 60 minutes,
the error code
L8
is output.
Inverter current
≤
23.8 A
Upper limit frequency = max Hz
10 sec.
Matching of frequency
Upper limit frequency: 1-step down
Upper limit frequency: 1-step up
Keeping the current step.
Not limited
Limited
Tfin
≥
78˚C (172.4˚F)
Tfin
≥
78˚C (172.4˚F)
Tfin
≥
83˚C (181.4˚F)
Fin temperature standby
&
&
Tfin
≤
75˚C (167˚F)
continues for 3 min.
Without conditions
(R19084)
When occurring 4 times within 60 minutes,
the error code
L4
is output.
Tfin < 75˚C (167˚F)
Upper limit frequency = max Hz
10 sec.
Matching of frequency
Upper limit frequency: 1-step down
Keeping the current step.
Upper limit frequency: 1-step up
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...