Troubleshooting for Outdoor Unit
SiUS181305E
203
Troubleshooting
7.18 Radiation Fin Temperature Rise
Error Code
L4
Method of Error
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Error Decision
Conditions
When the radiation fin temperature increases above 83°C (181.4°F)
Supposed
Causes
Defective main PCB (A1P)
Defective radiation fin thermistor (FINTH)
Troubleshooting
Refer to Thermistor Resistance / Temperature Characteristics table 2 on page 225.
YES
Faulty radiation from the power unit
∗
Blocked air suction port
∗
Stained radiation fin
∗
High outdoor temperature
NO
NO
YES
Replace the radiation fin thermistor.
NO
Replace the main PCB (A1P).
Continue operation.
It is supposed that the radiation fin
temperature became high due to
some field factors. In this
connection, check the following
points:
∗
Stained radiation fin
∗
Airflow obstructed with dirt or
foreign matters
∗
Damage to fan impellers
∗
Too high outdoor temperature
Turn OFF the power supply,
and then make measurement
of resistance of the radiation
fin thermistor.
Disconnect the connector
X111A and then properly
connect it.
YES
(R19094)
The radiation
fin temperature exceeds
83
°
C (181.4˚F).
Is the thermistor
resistance normal?
Does
the malfunction
recur when the power
supply turns ON to start
the compressor?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...