SiUS181305E
Troubleshooting for Outdoor Unit
Troubleshooting
190
7.6
Moving Part of Electronic Expansion Valve (Y1E, Y3E)
Abnormality
Error Code
E9
Method of Error
Detection
System checks if the connector is disconnected, and the detection is based on the continuity of
electronic expansion valve coil.
Error Decision
Conditions
No current is detected in the common (COM +) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve Y1E or Y3E
Defective moving part of electronic expansion valve
Defective main PCB (A1P)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...