Troubleshooting for Branch Provider (BP) Unit
SiUS181305E
181
Troubleshooting
6.5
Transmission Error between Outdoor Unit and Branch
Provider (BP) Unit
Error Code
UJ
Method of Error
Detection
Transmission error is detected when the outdoor unit could not received the data from BP unit
correctly.
Error Decision
Conditions
When the data from BP unit could not be correctly received continuously for 10 minutes
Supposed
Causes
Incorrect connection of transmission wire
Faulty outdoor unit power supply
Defective BP unit PCB
Defective outdoor unit PCB
Distortion of power supply waveform
Troubleshooting
Check No.11
Refer to P.182
YES
NO
YES
Check No. 11
Check the power supply
waveform.
NO
YES
(R15586)
NO
YES
Check the transmission wire
and the connection orders.
Could be other causes than
malfunction.
Probe where the noise comes
from, and apply remedy
required.
Replace the main PCB (A1P)
of the outdoor unit.
Probe the causes for
deformation of power supply
waveform and apply remedy
required.
Is it deformed?
Turn the power supply back
on.
Is it normal?
Is
UJ
displayed again?
NO
Replace the main PCB (A1P)
of the outdoor unit.
Is HAP on the
outdoor unit PCB
blinking?
Turn the power supply off.
Check the transmission wire
between outdoor unit - BP
unit
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...