Service Check Function
SiUS181305E
145
Troubleshooting
2. Service Check Function
2.1
CTXS, FTXS, CDXS, FDXS Series
Check Method 1
1. When the timer cancel button is held down for 5 seconds,
00
is displayed on the temperature
display screen.
2. Press the timer cancel button repeatedly until a long beep sounds.
The code indication changes in the sequence shown below.
Note:
1. A short beep or two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode, hold the timer cancel button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
3. Not all the error codes are displayed. When you cannot find the error code, try the check
method 2. (
No.
Code
No.
Code
No.
Code
1
00
13
C7
25
UA
2
U4
14
A3
26
UH
3
L5
15
H8
27
P4
4
E6
16
H9
28
L3
5
H6
17
C9
29
L4
6
H0
18
C4
30
H7
7
A6
19
C5
31
U2
8
E7
20
J3
32
EA
9
U0
21
J6
33
AH
10
F3
22
E5
34
FA
11
A5
23
A1
35
H1
12
F6
24
E1
36
P9
(R14460)
Timer cancel button
< ARC452 Series >
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...