SiUS181305E
Field Settings
Test Operation and Field Settings
96
2. Field Settings
2.1
Outdoor Unit
2.1.1 Setting Mode and Monitor Mode
Outline
The following 3 modes can be changed over with the button switches on the service PCB and you
can find the present mode by the status of the H1P indicator.
(1) Setting mode 1 (H1P off)
Initial status (normal) : Also indicates during abnormal.
(2) Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
(3) Monitor mode (H1P blinks)
Used to check the program made in setting mode 2.
H1P H3P
H5P H7P
H2P H4P H6P
(R15629)
BS1
(MODE)
BS2
(SET)
BS4
(TEST)
BS5
(RESET)
BS3
(RETURN)
Contents display
Monitor mode
Press the
BS3
(
RETURN
button).
Press the
BS3
(
RETURN
button).
Setting mode 2
Press the
BS3
(
RETURN
button).
Press the
BS3
(
RETURN
button).
Press the
BS3
(
RETURN
button).
Press the
BS1
(
MODE
button).
Press the BS1 (
MODE
button).
Press the
BS1
(
MODE
button).
Select a setting condition
with the
BS2
(
SET
button).
Select a setting item with
the
BS2
(
SET
button).
Select a check item with
the
BS2
(
SET
button).
Setting condition
(Contents) display
Setting mode 1
(Initial condition)
MODE
OFF
H1P
Press the
BS1
(
MODE
button) for more
than 5 seconds.
(R15657)
MODE
ON
H1P
H1P
Blinking
MODE
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...