manualshive.com logo in svg
background image

REMOVAL

PROCEDURE

S E R V I C E   M A N U A L

5.0/6.0/7.1/8.0/9.0 kW Class
24000/28000/33000 Btu/h Class

Outdoor Unit

Inverter

Pair Type

Si001166

Содержание RKS24HV2S

Страница 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L 5 0 6 0 7 1 8 0 9 0 kW Class 24000 28000 33000 Btu h Class Outdoor Unit Inverter Pair Type Si001166...

Страница 2: ...Service Manual Removal Procedure Outdoor Unit Applicable Models zCooling Only zHeat Pump RKS24HV2S RXS71KVM RKS28HV2S RXS80KVM RKS33HV2S RXS90KVM RKS71LVMA RXS24LVJU RXS71LVMA RXS60LAVMA RXS50LBVMA...

Страница 3: ...lectrical Box 14 3 Removal of PCBs 18 4 Removal of Fan Motor 21 5 Removal of Coils Thermistors 22 6 Removal of Sound Blankets 25 7 Removal of Compressor 28 Note The illustrations may be slightly diffe...

Страница 4: ...rocedure Points 1 Appearance features The design of discharge grille is different depending on the model 2 Remove the suction grille The hooks are secured in the clearances of the outdoor heat exchang...

Страница 5: ...ve the top panel 1 Remove the 4 screws on the back and the screw on the left side 2 Remove the 2 screws on the front and the screw on the right side panel 3 Lift the top panel and remove it Step Proce...

Страница 6: ...Removal Procedure 4 Remove the front panel 2 This screw is M5 3 16 1 Remove the 5 screws 2 Slide the front panel 2 downward to unfasten the hook 3 Remove the front panel 2 Step Procedure Points R1672...

Страница 7: ...cedure 5 5 Remove the right side panel 1 Remove the 2 screws Slide the right side panel downward to unfasten the 2 hooks on the rear side 2 Remove the right side panel Step Procedure Points R16728 Rig...

Страница 8: ...door fan first to remove the front panel 1 1 Remove the 4 screws on the discharge grille 2 Pull the bottom of the discharge grille 3 Slide the discharge grille downward to unfasten the 2 hooks at the...

Страница 9: ...f the outdoor fan Nut size M8 6 Remove the 2 screws on the partition plate 1 7 Remove the screw at the bottom left of the front 8 Remove the screw at the bottom of the left side Step Procedure Points...

Страница 10: ...re 9 Remove the screw at the bottom of the rear side 10 Lift the front panel 1 to unfasten the hook 11 Remove the front panel 1 Be sure to detach the front panel 1 carefully so as not to deform it Ste...

Страница 11: ...U S models only 1 Remove the 2 screws and remove the shield plate ASSY 2 Release the clamps of the connection wire 8 Remove the rear panel 1 Remove the screw on the partition plate 2 Step Procedure Po...

Страница 12: ...l Procedure 2 Slide the partition plate 2 to the left and remove it 3 Remove the 3 screws on the wire fixing plate 4 Remove the wire fixing plate and the insulation Step Procedure Points Hook R16743 R...

Страница 13: ...d the power supply wire 6 Release the holder of the outdoor temperature thermistor The holder is secured in the clearances of the outdoor heat exchanger fins 7 Release the harness of the outdoor tempe...

Страница 14: ...12 Removal Procedure 8 Remove the 3 screws on the rear panel 9 Remove the screw on the bottom frame 10 Remove the screw on the stop valve mounting plate Step Procedure Points Rear panel R16699 R16700...

Страница 15: ...Si001166 Removal of Outer Panels Removal Procedure 13 11 Lift the rear panel upward to unfasten the 2 hooks 12 Remove the rear panel Step Procedure Points Hook Hook R16702 R16703...

Страница 16: ...es or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the screw on the stop valve mounting plate 2 Remove the screw on the partition plate 1 3 Remove...

Страница 17: ...electronic expansion valve coil S40 overload protector S80 four way valve coil S90 thermistors When reassembling insert the clamp of the thermistor ASSY harness into the hole as below When reassembli...

Страница 18: ...f the thermistor harness from the hole of the electrical box 9 The compressor lead wire is fixed on the partition plate 1 with a clamp 10 Release the clamp of the compressor relay harness with pliers...

Страница 19: ...ocedure 17 11 Disconnect the relay connector for the compressor 12 Slide the electrical box to the left to unfasten the hook on the right side of the box 13 Lift up the electrical box and remove it St...

Страница 20: ...k Step Procedure Points 1 Disconnect the connectors S52 S102 from the service monitor PCB Preparation Remove the electrical box according to the Removal of Electrical Box 2 Detach the 4 clamps with pl...

Страница 21: ...minal board 6 Disconnect the harnesses 1 Black 2 White 3 Red L1 Black L2 Brown N1 White N2 Blue 7 Disconnect the 2 harnesses for the reactor HR1 HR2 HR1 White HR2 Blue The harness for HR2 has a ferrit...

Страница 22: ...moval of PCBs Si001166 20 Removal Procedure 8 Remove the 3 screws of the main PCB 9 Release the 4 hooks 10 Lift up and remove the main PCB Step Procedure Points Main PCB R5287 Hook R13524 Main PCB R52...

Страница 23: ...crews first Then remove the 2 upper screws Preparation Remove the electrical box according to the Removal of Electrical Box Be sure to remove the lower screws first If the top screws are removed first...

Страница 24: ...r more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the electronic expansion valve coil 1 Pull the electronic expansion valve coil out 2 Remove the fou...

Страница 25: ...ve the thermistors 1 Pull out the outdoor heat exchanger thermistor 2 Slightly open the sound blanket outer 3 Remove the sound blanket top upper Step Procedure Points Outdoor heat exchanger thermistor...

Страница 26: ...Removal of Coils Thermistors Si001166 24 Removal Procedure 4 Remove the discharge pipe thermistor Step Procedure Points Discharge pipe thermistor R9469...

Страница 27: ...supplies before disassembling work Step Procedure Points 1 Open the sound blanket outer 2 Remove the sound blanket top upper The sound blanket is fragile Carefully pass the discharge pipe through it...

Страница 28: ...und blanket top lower The sound blanket is fragile Carefully pass the discharge pipe through it 6 Open the sound blanket inner The sound blanket is fragile Be careful of the notches of the compressor...

Страница 29: ...Si001166 Removal of Sound Blankets Removal Procedure 27 7 Remove the sound blanket inner Step Procedure Points Sound blanket inner R7019...

Страница 30: ...edure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the terminal cover 2 Pull out the 3 lead wires 3 Remo...

Страница 31: ...y non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat Keep below 120 C For the sake of this w...

Страница 32: ...Revision History Month Year Version Revised contents 08 2012 Si001166 First edition...

Страница 33: ...ries supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and acce...