Si39-406
Installation
General Information
51
Wall Mounted
Type
(FXAQ-M)
(1) Install the drain piping. (Refer to Fig. 16)
The drain pipe should be short with a downward slope and should prevent air pockets from
forming.
Watch out for the points in the figure 16 when performing drain work.
When extending the drain hose, use a commercially available drain extension hose, and be
sure to insulate the extended section of the drain hose which is indoors.
(Refer to Fig. 17)
Make sure the diameter of the extension drain piping is the same as the indoor unit drain hose
(hard vinyl chloride, I.D. 9/16”) or bigger.
In case of converging multiple drain pipes, install them referring to Fig. 18.
Select diameter of drain piping which adapts to the capacity of the unit connected.
(2) Make sure the drain works properly.
After drain work is complete, perform a drain check by opening the front panel,
removing the
air filter
, pouring water into the drain pan, and making sure water flows smoothly out of the
drain hose.
(Refer to Fig. 19)
Caution
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in
the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain
pipe.
Fig. 16
Make sure the drain
hose is at a downward
slope.
Make sure the tip does
not go underwater even
when water is added.
Drain hose
Drain hose
(Downward
slope)
Indoor unit drain hose
Extension drain piping
(commercially available)
Insulating tube
(commercially available)
Insulating tape (accessory) (4)
( See “4.INDOOR UNIT INSTALLATION” )
Fig. 17
Fig. 18
(Slope of at least 1/100)
4 or more
Plastic container
for pouring
Drain pan
Make sure not to splash the water.
Fig. 19
Содержание REYQ96MTJU
Страница 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Страница 6: ...Si39 406 iv Table of Contents...
Страница 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Страница 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Страница 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Страница 124: ...Appendix Si39 406 118 General Information 7 8 Piping System Diagrams 7 8 1 Outdoor Unit REYQ96MTJU 4D045329...
Страница 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Страница 127: ...Si39 406 Appendix General Information 121 7 9 Wiring Diagrams 7 9 1 Outdoor Unit REYQ96MTJU 3D044892A...
Страница 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Страница 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Страница 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Страница 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Страница 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...