Specifications
SiBE37-701_B
57
Specifications
1.3
BS Units
Note:
★
1 When connecting with a 20 to 50 class indoor unit, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
★
2 When connecting with an indoor unit of 150 or more and 160 or less, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
Connection Range for BS Unit
Note:
★
Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from
double outdoor units, 130% from triple outdoor units.
Model
BSV4Q100PV1
BSV6Q100PV1
Power Supply
1 Phase 50Hz 200-240V
1 Phase 50Hz 200-240V
Total capacity index of connectable indoor
units
400 or less
600 or less
Capacity index of connectable indoor units
per branch
100 or less
No. of Connectable Indoor Units
Max. 20
Max. 30
Casing
Galvanized steel plate
Galvanized steel plate
Dimensions: (H×W×D)
mm
209×1053×635
209×1577×635
Sound Absorbing Thermal Insulation
Material
Foamed polyurethane, Flame resistant needle felt
Foamed polyurethane, Flame resistant needle felt
Piping
Connection
Indoor
Unit
Liquid Pipes
9.5mm C1220T (brazing connection)
★
1
9.5mm C1220T (brazing connection)
Gas Pipes
15.9mm C1220T (brazing connection)
★
1
15.9mm C1220T (brazing connection)
★
2
Outdoor
Unit
Liquid Pipes
12.7mm C1220T (brazing connection)
15.9mm C1220T (brazing connection)
Suction Gas Pipes
28.6mm C1220T (brazing connection)
28.6mm C1220T (brazing connection)
★
2
HP/LP Gas Pipes
19.1mm C1220T (brazing connection)
28.6mm C1220T (brazing connection)
★
2
Weight
kg
60
89
Standard Accessories
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Drawing No.
4D064131A
4D064132A
Components
Outdoor unit model name
Total capacity of connectable indoor
units
Number of connectable indoor
units
Indoor unit total capacity
REYQ8P
100 to 260 (400)
13 (20)
Same number of
BS units
REYQ10P
125 to 325 (500)
16 (25)
REYQ12P
150 to 390 (600)
19 (30)
REYQ14P
175 to 455 (700)
22 (35)
REYQ16P
200 to 520 (800)
26 (40)
REYQ18P
225 to 585 (720)
29 (36)
REYQ20P
250 to 650 (800)
32 (40)
REYQ22P
275 to 715 (880)
35 (44)
REYQ24P
300 to 780 (960)
39 (48)
REYQ26P
325 to 845 (1,040)
42 (52)
REYQ28P
350 to 910 (1,120)
45 (56)
REYQ30P
375 to 975 (1,200)
48 (60)
REYQ32P
400 to 1,040 (1,280)
52 (64)
REYQ34P
425 to 1,105 (1,105)
55 (55)
REYQ36P
450 to 1,170 (1,170)
58 (58)
REYQ38P
475 to 1,235 (1,235)
61 (61)
REYQ40P
500 to 1,300 (1,300)
64 (64)
REYQ42P
525 to 1,365 (1,365)
REYQ44P
550 to 1,430 (1,430)
REYQ46P
575 to 1,495 (1,495)
REYQ48P
600 to 1,560 (1,560)
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...