Part 6 Service Diagnosis
4.10 Broken Wire Check of the Relay Wires
CHECK 15
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short
circuit between the outdoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit A"
that is farthest from the central remote controller, and then conduct continuity
checks between the transmission wiring terminal blocks F1 and F2 of the central
remote controller using a multimeter. If there is continuity between the said terminal
blocks, the outdoor-outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the
outdoor-outdoor unit terminal of the "Outdoor Unit A" short circuited, conduct
continuity checks between the transmission wiring terminal blocks F1 and F2 of the
unified ON/OFF controller. If there is no continuity as well, conduct continuity
checks between the outdoor-outdoor unit terminal of the "Outdoor Unit E", between
the outdoor-outdoor unit terminal of the "Outdoor Unit D", between the
outdoor-outdoor unit terminal of the "Outdoor Unit C", … in the order described,
thus identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places
before the said place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for
checking the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for
broken wires)
Turn OFF the power supply to all equipment, short circuit between the
indoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit C, and then conduct
continuity checks between the transmission wirings F1 and F2 of the "Indoor Unit a"
that is farthest from the "Outdoor Unit C" using a multimeter. If there is continuity
between the said transmission wirings, the indoor-outdoor unit transmission wiring
has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the
indoor-outdoor unit terminal of the "Outdoor Unit C" short circuited, identify the
place with continuity in the transmission wiring of the "Indoor Unit b", transmission
wiring of the "Indoor Unit c", and transmission wiring of the "Indoor Unit d" in the
order described.
If the place with continuity can be identified, there may be broken wires in places
before the said place with continuity.
Содержание REYQ72-432XAYCU
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ72 456XATJU A REYQ72 456XAYDU A REYQ72 432XAYCU A SiUS371901EB ...
Страница 92: ...Refrigerant Circuit Piping Diagrams SiUS371901EB 85 Part 2 Refrigerant Circuit BSF6Q54TVJ 3D125655 ...
Страница 93: ...SiUS371901EB Refrigerant Circuit Piping Diagrams Part 2 Refrigerant Circuit 86 BSF8Q54TVJ 3D125656 ...
Страница 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Страница 456: ...Wiring Diagrams SiUS371901EB 449 Part 7 Appendix REYQ72 96 120XAYDU REYQ72 96 120XAYDA 2D119207C ...
Страница 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Страница 458: ...Wiring Diagrams SiUS371901EB 451 Part 7 Appendix REYQ72 96 120 144 168XAYCU REYQ72 96 120 144 168XAYCA 2D119209B ...
Страница 459: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 452 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B ...
Страница 460: ...Wiring Diagrams SiUS371901EB 453 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A ...
Страница 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Страница 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Страница 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Страница 465: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 458 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C ...
Страница 466: ...Wiring Diagrams SiUS371901EB 459 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Страница 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Страница 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Страница 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Страница 477: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 470 1 4 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B ...
Страница 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Страница 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Страница 480: ...Wiring Diagrams SiUS371901EB 473 Part 7 Appendix 1 4 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A ...
Страница 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...