Check
SiUS372201EA
425
Part 6 Service Diagnosis
Note(s)
4.2 Low Pressure Check
CHECK 2
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points
Abnormal drop in
low pressure
(Low evaporating
temperature)
[In cooling]
(
1.)
Defective
low pressure
control
Defective
compressor
capacity
control
Defective low pressure
sensor
Defective outdoor unit
main PCB
Defective outdoor unit
main PCB
Defective outdoor unit
main PCB
Defective outdoor unit
main PCB
Defective
low pressure
protection
control
Defective low pressure
sensor
Defective hot gas
solenoid valve
[In both cooling
and heating]
(
2.)
[In cooling]
If the indoor unit
electronic
expansion valve is
excessively
throttled: (
3.)
Defective indoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
Defective
control
Defective gas pipe
thermistor of indoor unit
Defective liquid pipe
thermistor of indoor unit
Defective outdoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
[In heating]
If the outdoor unit
electronic
expansion valve
is excessively
throttled:
(
4.)
Defective
control
Defective low pressure
sensor
Defective suction pipe
thermistor
[In cooling]
Low suction air
temperature of
the evaporator
[In heating]
Low suction air
temperature of
indoor unit
Short circuit
Low room temperature
Defective suction air thermistor of indoor unit
Low suction air temperature of outdoor unit
Defective outdoor air temperature thermistor of outdoor unit
High pipe
resistance
Abnormal piping length
Bent or crashed pipe
Clogging of foreign materials
Stop valve closed
Less
circulation
quantity of
refrigerant
Degradation
in evaporating
capacity
Refrigerant shortage
Moisture choke
Dirty
evaporator
Decreased
airflow rate
Decreased
fan output
Defective fan motor
Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation normal?
If a spare PCB is mounted, is the
capacity setting properly made?
Is the air filter clogged?
Is there any obstacle in the airflow passage?
Defective outdoor unit main
PCB (Including capacity setting)
High
airflow
passage
resistance
Dirty filter
Obstacle
Defective electronic
expansion valve
control
Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
Are the voltage characteristics normal?
Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
Are the coil resistance and insulation normal?
Are the voltage characteristics normal?
Are the coil resistance and insulation normal?
Check for the thermistor resistance and connection.
Check for the thermistor resistance and connection.
Are the voltage characteristics normal?
Are the coil resistance and insulation normal?
Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
Check for the thermistor resistance and connection.
Is the suction air temperature more than 14°C (57.2°F)?
Is the room temperature less than 14°C (57.2°F)?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Is the outdoor air temperature more than –20°C (–4°F)?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Does the piping length fall in the permissible range?
Conduct visual checks for pipe conditions.
Is there any temperature difference caused before
and after the filter or branch pipe?
Check if the stop valve is open.
Refer to
CHECK 7
.
Eliminate moisture by vacuum operation. (Refer to
CHECK 8
)
Is the heat exchanger clogged?
1. For details of compressor capacity control while in cooling, refer to Compressor PI control.
2. The low pressure protection control includes low pressure protection control and hot gas
bypass control.
3. In cooling, the indoor unit electronic expansion valve is used for superheating degree control.
4. In heating, the outdoor unit electronic expansion valve (main) is used for superheating
degree control of outdoor heat exchanger.
Содержание REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Страница 433: ...SiUS372201EA Check Part 6 Service Diagnosis 426 Reference Reference CHECK 7 Refer to page 432 CHECK 8 Refer to page 433...
Страница 460: ...Wiring Diagrams SiUS372201EA 453 Part 7 Appendix REYQ72 96 120 144 168 192 216 240AAYDA C 2D131905G...
Страница 463: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 456 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Страница 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Страница 468: ...Wiring Diagrams SiUS372201EA 461 Part 7 Appendix 1 2 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A...
Страница 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Страница 470: ...Wiring Diagrams SiUS372201EA 463 Part 7 Appendix 1 3 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 471: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 464 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 478: ...Wiring Diagrams SiUS372201EA 471 Part 7 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 480: ...Wiring Diagrams SiUS372201EA 473 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Страница 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...