17
RELQ-TATJA / TAYDA / TAYCA
EDUS371705C-D
8. Capacity Range
8.1 Connection Ratio
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Type
Min.
connection
ratio
Max. connection ratio
Types of connected indoor units
Type of connected air treatment
equipment
When using only
FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54TA
When using at least one
FXZQ05TA, FXSQ05TA,
FXFQ07/09
When using other
indoor unit models
FXMQ-MF
When FXMQ-MF is
only connected
When FXMQ-MF
and indoor units
are connected
Single outdoor units
70%
200% *1
180% *1
200% *1
100%
100% *2 *3
Double outdoor units
160% *1
160% *1
Notes:
*1. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units. Field setting now exists to
configure this situation. For cooling and heating mode – see below.
*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air
processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
*3. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further
details.
*4. For indoor units used for cooling only (do not connect to Branch Selector unit when using for heat recovery), total capacity index must be 70%
or less than the capacity index of the outdoor units.
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
Default value = 0
Value
Indoor unit fan tap setting
0
Fan speed is limited to L tap when indoor units capacity
≥
130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity
≥
130%.
2
Fan speed follows the setting of remote controllers (not limited by indoor units connection capacity).
3
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C) and indoor air temperature is in
condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over 90.5 °F (32.5°C) or indoor air
temperature is in condition B (**).
4
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C) and indoor air temperature is in
condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over 79.7°F (26.5°C) or indoor air
temperature is in condition B (**).
5
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C) and indoor air temperature is in
condition A (*). It returns to remote controller setting when outdoor air temperature goes up to over 72.1°F (22.3°C) or indoor air
temperature is in condition B (**).
6
Fan speed is limited to L tap when outdoor air temperature goes down to below 85.1°F (29.5°C). It returns to remote controller
setting when outdoor air temperature goes up to over 90.5°F (32.5°C).
7
Fan speed is limited to L tap when outdoor air temperature goes down to below 74.3°F (23.5°C). It returns to remote controller
setting when outdoor air temperature goes up to over 79.7°F (26.5°C).
8
Fan speed is limited to L tap when outdoor air temperature goes down to below 66.7°F (19.3°C). It returns to remote controller
setting when outdoor air temperature goes up to over 72.1°F (22.3°C).
* Indoor condition A: Temperature difference (indoor air temperature - set temperature) is more than −2.7°F (−1.5°C) and less than 5.4°F (3°C).
** Indoor condition B: Temperature difference (indoor air temperature - set temperature) is −2.7°F (−1.5°C) or less, or 5.4°F (3°C) or more.
Содержание RELQ-TATJA Series
Страница 2: ......
Страница 32: ...30 RELQ TATJA TAYDA TAYCA EDUS371705C D 12 Center of Gravity RELQ72TATJA TAYDA TAYCA 4D107384 ...
Страница 33: ...31 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96 120TATJA TAYDA TAYCA 4D107385 ...
Страница 35: ...33 RELQ TATJA TAYDA TAYCA EDUS371705C D 14 Piping Diagrams RELQ72TATJA TAYDA TAYCA 3D107166 ...
Страница 36: ...34 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96 120TATJA TAYDA TAYCA 3D107167 ...
Страница 52: ...50 RELQ TATJA TAYDA TAYCA EDUS371705C D 18 Operation Limits RELQ72 240TATJA TAYDA TAYCA 3D107374 ...
Страница 54: ...52 RELQ TATJA TAYDA TAYCA EDUS371705C D 20 Sound Levels Reference Data RELQ72TATJA TAYDA TAYCA 4D107376A ...
Страница 55: ...53 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96TATJA TAYDA TAYCA 4D107377A ...
Страница 56: ...54 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ120TATJA TAYDA TAYCA 4D107378A ...
Страница 64: ...62 RELQ TATJA TAYDA TAYCA EDUS371705C D 23 Caution Label 23 1 RELQ72 240TATJA TAYDA TAYCA 3P558142 1B ...
Страница 65: ...63 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 66: ...64 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 67: ...65 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 68: ...66 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 69: ...67 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 70: ...68 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Страница 71: ...69 RELQ TATJA TAYDA TAYCA EDUS371705C D 3P385987 1A ...
Страница 72: ...70 RELQ TATJA TAYDA TAYCA EDUS371705C D 3P385987 1A ...
Страница 83: ......