
IM 893-10 • ROOFPAK SINGLEZONE UNITS 92 www.DaikinApplied.com
u
nIT
o
PTIons
MicroTech III Remote User Interface
for Daikin Rooftop and Self-Contained Systems
In addition to the unit-mounted user interface provided with
MicroTech III controls, Daikin applied rooftop systems and
indoor vertical self-contained systems can be equipped with
a remote user interface that handles up to eight units per
interface. The remote user interface provides convenient
access to unit diagnostics and control adjustments, without
having to access your roof or mechanical rooms located on
each floor.
Each remote user interface offers the same functionality as its
unit-mounted counterpart, including:
• Push-and-roll navigation wheel with an 8-line by 30
character display format.
• Digital display of messages in English language.
• All operating conditions, system alarms, control
parameters and schedules are monitored.
Features
• Can be wired up to 700 meters from units for flexibility in
placing each remote user interface within your building.
• Unit and remote user interfaces are both active.
Figure 98: Remote User Interface
Figure 99: Process Bus Wiring Connections
Unit #1 MCB
Unit #2 MCB
Unit #3 MCB
Re mote HMI
CE +
CE-
CE +
CE-
+
E
C
+
E
C
-
E
C
-
E
C
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
Daisy-chain up to 8 units to a
single remote interface
Содержание RDT
Страница 60: ...IM 893 10 ROOFPAK SINGLEZONE UNITS 60 www DaikinApplied com Wiring Diagrams Figure 64 VFD Control SAF and RAF...
Страница 61: ...Wiring Diagrams www DaikinApplied com 61 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 65 VAV Control Inputs...
Страница 65: ...Wiring Diagrams www DaikinApplied com 65 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 67 Electric Heat Control...