Table 19: Propeller Exhaust Fan Troubleshooting
Problem
Cause
Corrective Action
Reduced Airflow
System resistance is too high.
• Check backdraft dampers for proper operation
• Remove obstructions in ductwork
• Clean dirty filters
• Check for adequate supply for air exhaust fans or
exhaust air for supply fans
Unit running backwards.
See Prestarting Checks on page 87
Fan speed too low.
Increase fan speed
Excessive dirt on propeller.
Clean propeller
Excessive Noise
Bearings
• Tighten bearing collars and setscrews
• Lubricate bearings
• Replace defective bearings
V-Belt drive
• Tighten pulleys on motor shaft and fan shaft
• Adjust belt tension
• Align pulleys
• Replace worn belts or pulleys
Excessive vibration
• Clean dirt build-up from propeller
• Check all setscrews and fasteners for tightness
• Check for worn bearing
• Correct propeller imbalance
• Check for loose dampers, guards or ductwork
Defective motor
Replace motor.
Figure 95: Propeller Exhaust Fan Replacement Parts List
9
8
7
1 0
6
5
4
1
2
3
1. F an pa n e l
2. P rop e l
l er
3. D rive fr ame
ch a n n e l ( 2)
4. M oto r pl ate
5. M oto r
6. M oto r pu lley
7. S h a ft pu l
l ey
8. F an sh aft
9. B e a rin g s
10. B elt
11. B
a
e ring pl ate
11
Содержание RDT
Страница 60: ...IM 893 10 ROOFPAK SINGLEZONE UNITS 60 www DaikinApplied com Wiring Diagrams Figure 64 VFD Control SAF and RAF...
Страница 61: ...Wiring Diagrams www DaikinApplied com 61 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 65 VAV Control Inputs...
Страница 65: ...Wiring Diagrams www DaikinApplied com 65 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 67 Electric Heat Control...