IM 893-10 • ROOFPAK SINGLEZONE UNITS 16 www.DaikinApplied.com
I
nTroduCTIon
FanTrol
The FanTrol, provided on all units, is a method of head
pressure control that automatically cycles the condenser fans
in response to ambient air temperature. This feature maintains
head pressure and allows the unit to run at low ambient air
temperatures.
RPS/RDT and RCS units have two independent refrigerant
circuits with one to four condenser fans being controlled
independently by the ambient air temperature of each circuit.
See the following sections for sequence of operation for
condenser fans with FanTrol.
FanTrol does not apply to units with VFD compressors.
Table 3: R-410A FanTrol Setpoints in °F with
MicroTech III Controls.
Unit
Size
Degrees Farenheit
D07a
D08b
PC13/PC23c
Setpoint Differential Setpoint Differential Setpoint Differential
015
70
5
016
75
5
020
70
5
021
75
5
025
60
5
026
70
5
030
75
5
031
75
5
035
70
5
040
65
5
042
65
5
045
65
5
050
65
5
051
70
5
061
60
5
063
70
5
068
70
5
070
75
5
90
35
071
75
5
90
35
075
65
5
85
5
90
35
079
65
5
80
5
90
35
080
75
5
90
35
081
75
5
90
35
085
70
5
90
35
090
60
5
85
5
90
35
091
60
5
85
5
90
35
100
60
5
85
5
90
35
101
60
5
85
5
90
35
105
50
5
80
5
90
35
110
65
5
90
5
90
35
120
65
5
85
5
90
35
125
65
5
85
5
90
35
130
60
5
85
5
90
35
140
55
5
80
5
90
35
a. D07 = TC12
b. D08 = TC14
c. PC13/23 Cut in = 450 psig (125 degree sat.), fixed
Cut out = 275 psig (90 degree sat.), fixed