Charging Charts
Figure 17: 6-1/2 Ton Charging Charts
115
105
95
85
75
65
55
175
200
225
250
275
300
325
350
375
400
425
450
475
500
100.0 105.0 110.0 115.0 120.0 125.0 130.0 135.0 140.0 145.0 150.0 155.0 160.0 165.0
A/C SYSTEM CHARGE CHART
CAUTION: RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS BEFORE FINAL REFRIGERANT CHECK!
INSTRUCTIONS: 1. MEASURE PRESSURE AT COMPRESSOR SUCTION AND LIQUID.
2. MEASURE OUTDOOR AMBIENT TO UNIT.
3. PLACE AN “X” ON THE CHART WHERE THE SUCTION AND LIQUID INTERSECT.
4. IF “X” IS BELOW OUTDOOR AMBIENT TEMPERATURE LINE, ADD CHARGE AND REPEAT STEPS 1-3.
5. IF “X” IS ABOVE AMBIENT TEMPERATURE LINE, RECOVER EXCESS CHARGE AND REPEAT STEPS 1-3.
92-102644-17-00
Vapor Pressure (PSIG)
Pressure at Liquid Service Port (PSIG)
Outdoor Ambient
(°F DB)
Charging Charts
www.DaikinApplied.com
21
IM 962-4 • AIR-COOLED SPLIT SYSTEM CONDENSERS