
Troubleshooting by Remote Controller
Si20-701_B
343
3.82
PJ
Defective Capacity Setting
Remote Controller Display
PJ
Applicable Models
RZQG
Method of Error Detection
Check whether set value written in E
2
PROM (at factory)
or set value of capacity setting adaptor (for spare) is the
same as outdoor unit capacity.
Error Decision Conditions
When the set value on E
2
PROM differs from the outdoor
unit capacity or a capacity setting adaptor except for PCB
applicable models is installed. (Error decision is made
only when turning the power supply ON.)
Supposed Causes
Improper set value of E
2
PROM
Improper capacity setting adaptor
Mismatching of type of PCB