Si33-105
Outline of Control (Outdoor Unit) < Symbols using in this manual >
Function R407C PLUS Series Heat Recovery System
57
3.3.2
4-Way Valve Changeover Ensuring Control
Purpose
!
To ensure the changeover 4-way valve, when difference in high and low pressure does not
generate due to mid-stop of the 4-way valve in each startup mode, increases the circulation
amount of compressor and forcibly generates the differential pressure with pressure loss in
the 4-way valve.
Contents
!
Varies the compressor loads under the following conditions in all startup control, 4-way valve
changeover control, and equalizing control.
Computes Pc-Pe every 10 seconds when 20 seconds elapsed after the control turns on, and
varies the compressor operation steps depending on the computed value.
When the following condition is met, conducts step down.
When stepping down, the lower-limit frequency is to be as follows.
At the normal startup of cooling and heating operation
Within 1 minute after startup : 41Hz + OFF + (OFF)
Elapsed time of 1 minute after startup : 52Hz+OFF+(OFF)
At the startup of 4-way valve changeover
41Hz + OFF + (OFF)
At the (startup of) pressure equalizing
41Hz + OFF + (OFF)
In any cases, fix the frequency in the initial compressor operation step at 41Hz + OFF +
(OFF).
Pc-Pe<0.196MPa
10-sec. timer counts up
Current compressor operation step + 3
However, the upper-limit frequency should
be 41Hz + ON + (OFF)
&
(V2564)
Pc-Pe>0.39MPa
Current compressor operation step – 3
(V2565)
Содержание R407C PLUS
Страница 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Страница 11: ...Introduction Si33 105 x ...
Страница 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Страница 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Страница 158: ...Si33 105 Troubleshooting by Remote Controller Troubleshooting R407C PLUS Series Heat Recovery System 147 ...
Страница 160: ...Si33 105 Troubleshooting by Remote Controller Troubleshooting R407C PLUS Series Heat Recovery System 149 ...
Страница 229: ...Troubleshooting OP Unified ON OFF Controller Si33 105 218 Troubleshooting R407C PLUS Series Heat Recovery System ...
Страница 232: ...Si33 105 Piping Diagram Appendix R407C PLUS Series Heat Recovery System 221 RSEYP24 26 28 30KJY1 3D031938 ...
Страница 234: ...Si33 105 Piping Diagram Appendix R407C PLUS Series Heat Recovery System 223 BSVP250KJV1 4D014499A ...
Страница 237: ...Wiring Diagram Si33 105 226 Appendix R407C PLUS Series Heat Recovery System RSEYP24 26 28 30KJY1 3D031467 ...
Страница 238: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 227 2 2 BS Unit 3D014829B ...
Страница 240: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 229 FXYFP32 40 50 63 80 100 125KVE 3D020238B ...
Страница 241: ...Wiring Diagram Si33 105 230 Appendix R407C PLUS Series Heat Recovery System FXYCP20 25 32 63KV1 DU229 5139C ...
Страница 242: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 231 FXYCP40 50 80 125KV1 DU230 522C ...
Страница 243: ...Wiring Diagram Si33 105 232 Appendix R407C PLUS Series Heat Recovery System FXYKP25 32 40 63KV1 DU227 544C ...
Страница 244: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 233 FXYSP20 25 32 40 50 63KV1 DU227 545E ...
Страница 245: ...Wiring Diagram Si33 105 234 Appendix R407C PLUS Series Heat Recovery System FXYSP80 100 125KV1 DU230 519D ...
Страница 246: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 235 FXYMP40 50 63 80 100 125KV1 DU229 5140C ...
Страница 247: ...Wiring Diagram Si33 105 236 Appendix R407C PLUS Series Heat Recovery System FXYMP200 250KV1 3D011012B ...
Страница 248: ...Si33 105 Wiring Diagram Appendix R407C PLUS Series Heat Recovery System 237 FXYHP32 63 100KV1 DU228 531C ...
Страница 249: ...Wiring Diagram Si33 105 238 Appendix R407C PLUS Series Heat Recovery System FXYAP20 25 32 40 50 63KV1 DU221 561F ...
Страница 263: ...Si33 105 iv Index ...