3
|
Components
Service manual
123
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Is the problem solved?
Action
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove the intelligent eye sensor wiring harness
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Disconnect the wiring harness from the intelligent eye sensor (PCB).
2
Disconnect the wiring harness connector from the indoor unit main PCB.
3
Cut all tie straps (if any) that fix the wiring harness.
4
Route the wiring harness out of the harness retainers and remove the
intelligent eye sensor wiring harness.
5
To install the intelligent eye sensor wiring harness, see
122].
To install the intelligent eye sensor wiring harness
1
Connect the wiring harness connector to the indoor unit main PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
2
Route the wiring harness through the appropriate harness retainers towards
the intelligent eye sensor (PCB).
3
Connect the wiring harness to the intelligent eye sensor (PCB).
4
Fix the wiring harness using new tie straps (if needed).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.12 Main PCB
3.12.1 Class 20~35 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.