12
|
Commissioning
Installer reference guide
60
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
The
stop valves
(gas and liquid) on the outdoor unit are fully open.
Initialization of the Multi system can take several minutes depending on the
number of indoor units and options used.
12.5.1 About wiring error check
INFORMATION
This function is available only for the air-conditioning indoor units. DHW tank wiring
MUST be check manually, automatic correction is NOT possible.
The wiring error check function will check and automatically correct any wiring
errors. This is useful for checking wiring that CANNOT be checked directly, such as
underground wiring.
This function CANNOT be used within 3 minutes after activating the safety breaker
or when the outside air temperature is ≤5°C and if water temperature in DHW tank
is ≥20°C.
To perform a wiring error check
INFORMATION
You only have to perform a wiring error check if you are not sure that the electrical
wiring and piping is connected correctly.
1
Remove the service PCB switch cover.
1×
1
A
1
2
3
4
5
SW3
2
2
Press shortly the wiring error check switch (SW3) on the outdoor unit service
PCB.
Result:
The service monitor LEDs indicate whether correction is possible or
not. For details about how to read the LED display, refer to the service
manual.
Result:
Wiring errors will be corrected after 15-20 minutes. If automatic correction
is not possible, check the indoor unit wiring and piping in the usual way.
Содержание Multi+ R32 Split Series
Страница 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Страница 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...