9
|
Electrical installation
Installer reference guide
52
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
1-3
9.1.3 Specifications of standard wiring components
Component
Power supply cable
Voltage
220~240 V
Current
16.3 A
Phase
1~
Frequency
50 Hz
Wire size
MUST comply with national wiring
regulation
3-core cable
Wire size based on the current,
but not less than 2.5 mm
2
Interconnection cable
(indoor↔outdoor)
Voltage
220~240 V
Wire size
Only use harmonised wire
providing double insulation and
suitable for applicable voltage
4-core cable
Minimum 1.5 mm
2
Recomended circuit breaker
20 A
Earth leakage circuit breaker / residual
current circuit breaker
MUST comply with national wiring
regulation
Electrical equipment must comply with EN/IEC 61000-3-12, the European/
International Technical Standard setting the limits for harmonic currents produced
by equipment connected to public low-voltage systems with input current >16 A
and ≤75 A per phase.
9.2 To connect the electrical wiring to the outdoor unit
1
Remove the switch box cover (1 screw).
1
2
1×
2
Strip insulation (20 mm) from the wires.
a
b
Содержание Multi+ R32 Split Series
Страница 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Страница 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...