![Daikin Multi+ R32 Split Series Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/daikin/multi-r32-split-series/multi-r32-split-series_installers-reference-manual_4701102037.webp)
7
|
Piping installation
Installer reference guide
37
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
a
b
a
Cut exactly at right angles.
b
Remove burrs.
3
Remove the flare nut from the stop valve and put the flare nut on the pipe.
4
Flare the pipe. Set exactly at the position as shown in the following figure.
A
Flare tool for R32
(clutch type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A
0~0.5 mm
1.0~1.5 mm
1.5~2.0 mm
5
Check that the flaring is properly made.
a
b
c
a
Flare’s inner surface MUST be flawless.
b
The pipe end MUST be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
7.2.6 Connections between outdoor and indoor unit using reducers
Total indoor air conditioning units capacity class that can be connected to this
outdoor unit
≤9.0 kW
Port
Dimensions
Class
Reducer
A
Liquid Ø6.4 mm
Gas Ø9.5 mm
15, 20, 25, 35, (42)
(a)
—
B+C
Liquid Ø6.4 mm
Gas Ø12.7 mm
15, 20, 25, 35, (42)
(a)
1+2 (accessory)
42, 50, 60
—
71
(b)
ASYCPIR
To tank
Liquid Ø6.4 mm
Gas Ø9.5 mm
90, 120
—
(a)
Only in case of connection with FTXM42R.
(b)
Only for connection with FBA71A9. Use option ASYCPIR for liquid (Ø9.5 mm→Ø6.4 mm)
and gas (Ø15.9 mm→Ø12.7 mm) piping.
1
2
Ø12.7 mm → Ø9.5 mm
Содержание Multi+ R32 Split Series
Страница 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Страница 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...