Unit installation
Installer reference guide
27
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
a
b
c
c
d
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
It is recommended to provide at least 150 mm of free space below the unit
(300 mm for heavy snowfall areas). Additionally, make sure the unit is positioned at
least 100 mm above the maximum expected level of snow. If necessary, construct
a pedestal. See
"6.3 Mounting the outdoor unit"
28] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
6.2 Opening the unit
6.2.1 About opening the unit
At certain times, you have to open the unit.
Example:
▪
When connecting the refrigerant piping
▪
When connecting the electrical wiring
▪
When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
6.2.2 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Содержание Multi+ R32 Split Series
Страница 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B9...
Страница 31: ...6 Unit installation Installer reference guide 31 4MWXM A9 R32 Split series 4P708645 1 2022 09...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ...4P708645 1 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...