6
|
Unit installation
Installer reference guide
26
4MWXM-A9
R32 Split series
4P708645-1 – 2022.09
b
c
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
▪
Height of windbreaker≥1.5×height of outdoor unit
▪
Mind the service space requirements when installing the windbreaker.
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient
temperatures within the following ranges (unless otherwise specified in the
operation manual of the connected indoor unit):
DX operation range
Cooling mode
Heating mode
–10~46°C DB
–15~24°C DB
DHW operation range
–15~42°C DB
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.