background image

Daikin

 IM 1019

5

Installation Instructions

5

On the circuit board, set the voltage selection switch 
(

Figure 3

) to the appropriate position prior to application 

of power.

24V =  24 VAC

110-277 V = 120, 240 or 277 VAC

Note: 

The circuit board is shipped with the voltage 
selection switch in the 110-227 V position. For 24
VAC use, the switch must be in the 24 V position

6

The circuit board is also equipped with configuration 
jumpers (JP1, JP3, and JP4 in 

Figure 3

). Depending on 

the application, it may be necessary to reconfigure the 
following jumpers:

JP1 Jumper Selection – Remote Temperature Sensor 

Local Sensing – Install JP1

Remote Sensing – Remove JP1 – Accessory sensors are 
available in standard 60" lengths but can be extended to 
meet application requirements. 

JP3 Jumper Selection – HVAC Setback Systems 

The JP3 jumper allows the T180 to be configured for 
Setback, Occupancy Detection or Door Switch Only 
Occupancy Operations. For further descriptions of these 
conditions please see the 

Technical and Application 

Notes‚ page 12

.

• Setback Operation - Remove JP3

• Occupancy Detection - Install JP3

• Door Switch Only - Install JP3

JP4 Jumper Selection – 2 or 4 Pipe Operation 

Connection of a pipe sensor will change the operation of 
the outputs as shown i

Table 4

. (See Technical Notes for 

further information on 

Pipe Sensor Operation‚ page 12

)

• 2-Pipe Operation - Install JP4 - The thermostat will per-

manently disable the Secondary Output and disables sys-
tem and fan invalid modes. 

• 4-Pipe Operation - Remove JP4 - Both the Main Output

(COOL) and Secondary Output (HEAT) will be avail-
able.

7

Connect the color coded thermostat wires (

Figure 4

) to 

the line voltage wires located in the mud ring/connection 
box and secure the connections with wire nuts.

8

Install the thermostat base to the mud ring/outlet box 
using two furnished mounting screws. Tighten the 
screws evenly but do not over tighten.

Note: 

An output ratings chart (

Table 5

) is located on the 

inside of the base.

9

With the base now secured, verify that the circuit board 
is firmly snapped into the cover and is not dislodged.

10

Install the cover assembly to the base, pressing firmly to 
engage the cover locking snaps.

Figure 4: Wiring Diagram 

Table 4: Jumper Activation

JP4 

Section

Pipe 

Sensor 

Water 

Temp

Aqua 

Stat

Main 

Output 

(Blue Wire)

Secondary 

Output 

(Red wire)

2-Pipe 

JP4-ON

Cold

Open

Cooling 

Only

Disabled

Hot

Closed

Heating Only

Disabled

2-Pipe 

JP4-OFF

Cold

Open

Cooling

Heating

Hot

Closed

Heating Only

Disabled

Note: 

*Fan will not cycle on for disabled modes.

Table 5: Output Ratings

Output Ratings

Voltage

FLA

LRA

RES 

AMPS

PILOT 

DUTY

HP

24 VAC

NA

NA

NA

24 VA

NA

120 VAC

5.8

34.8

6.0

125 VA

¼

240 VAC

2.9

17.4

5.0

125 VA

¼

277 VAC

2.4

14.4

4.2

125 VA

¼

Combined Load Current Not to Exceed 20 Amps

Содержание MT 180

Страница 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Страница 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Страница 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Страница 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Страница 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Страница 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Страница 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Страница 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Страница 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Страница 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Страница 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Страница 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Страница 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Страница 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Страница 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Страница 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Страница 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Страница 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Отзывы: