background image

4

Daikin

 IM 1019

Installation Instructions

Thermostat Model and Part Number

Optional Sensors/Kits

In addition to the T180 thermostat, 

Daikin

 offers optional 

sensors for occupancy detection (

page

 

14

 and 

page

 

15

) and 

10K pipe sensor 

page

 

12

) that can be ordered and used in 

conjunction with the thermostat. Use the associated kit 
number(s) provided in 

Table

 

3

 when ordering.

Installing, Mounting and Wiring 
the Thermostat

The thermostat should be used indoors only. It should be 
mounted on an inner wall in a location with freely circulating 
air, and where it will be responsive to changes in room 
temperature. Avoid mounting near heat generating appliances 
(i.e. TV, heater, refrigerator), or in direct sunlight.

The thermostat base mounts to a field provided 4" × 4" outlet 
box with a 2" × 4" horizontal mud ring. The thermostat cover 
assembly mounts to the thermostat base.

.

1

Disconnect power before installing or servicing.

2

Run line voltage wiring (and low voltage wiring if 
applicable) into the field provided outlet box and mud 
ring (

Figure 2

).

3

Locate all connections within the mud ring/connection 
box and wire nut all unused wires.

4

Remove the thermostat cover assembly from its base to 
gain access to the circuit board (

Figure 3

).

Figure 2: Mounting the Thermostat 

Figure 3: Circuit Board 

Daikin

 offers two different  7-Day Programmable Digital 

Heating/Cooling Thermostat with constant fan or Fan cycled, 
On/Off Valve Control depending on the fan speed control 
used (See 

Table

 

2

).

Table 2: Thermostat Model and Part Number

Model 

Number

Part 

Number

Fan Speed Control

TA180-001

910119110

3-speed fan control

TB180-001

910119111

Staged fan control

Table 3: Sensor Model and Kit Numbers

Sensor Model Number

Daikin

 Part Number

Occupancy 

Detection 

Sensor

SB200-001

6677877311

SD200-001

6677877411

SD200-002

6677877511

10K Pipe Sensor

107201601

 CAUTION

Before applying power, the voltage selection switch must be in 
the appropriate position. Failure to select the correct voltage 
can cause thermostat malfunction or permanently damage the 
thermostat.

 CAUTION

To use a remote sensor on units with local sensing capability, 
remove jumper JP1 to disable local sensing. Failure to remove 
JP1 can cause improper operation of the thermostat with a 
remote probe installed.

 CAUTION

• Use copper wire only. Insulate or wire nut all unused leads.
• Avoid electrostatic discharge to the thermostat.
• Failure to do so can cause thermostat malfunction or

permanently damage the thermostat.

 DANGER

Hazardous voltage. Combined load current is not to exceed 20 
amps. Mount only to a grounded metallic box.
Low voltage wiring is Class 2. To avoid electrical shock or
Damage to equipment, disconnect power before installing or 
servicing. Failure to follow these instructions will result in death 
or serious injury

Содержание MT 180

Страница 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Страница 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Страница 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Страница 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Страница 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Страница 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Страница 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Страница 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Страница 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Страница 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Страница 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Страница 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Страница 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Страница 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Страница 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Страница 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Страница 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Страница 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Отзывы: