background image

Daikin

 IM 1019

11

Operation

System Check-out

To verify thermostat operation after mounting and wiring it, 
perform the following:

1

Energize the system. 

2

Set fan to ON. Select each fan speed (TA180 Models) to 
verify operation.

3

Set the System button to AUTO, or available selection.

4

Using the UP arrow, adjust temperature more than 5°F 
above the room temperature to cycle on heating.

5

Using the DOWN arrow adjust the temperature to 5°F 
below room temperature to cycle on cooling.

Note: 

If the thermostat is set to utilize a time-based purge 
cycle (Service menu 16), the thermostat will conduct 
a 3-min purge on initial start-up if a pipe sensor is 
connected.

Condensate Overflow Interrupt

The remote probe input can be used with a condensate 
overflow interrupt switch (CO), either in conjunction with a 
remote probe (normally closed CO switch) or with local 
sensing (normally open CO switch). When the condensate 
switch activates, the T180 will display the service wrench and 
disable all outputs.

Figure 7: Remote probe installation

Figure 8: Local sensor installation 

Thermostat configuration/ Service Menu

To enter the Service Menu press the UP and DOWN arrows 
simultaneously for five (5) seconds. The current display icon 
will be turned off.

Service menu number 1 will appear. Push the SYSTEM button 
to move to the next Service Menu number. The UP and 
DOWN arrow keys will scroll through your range of options 
for each feature. All changes to the Service Menu are 
automatically saved when the system times out. Please refer to 
the service menu table (

Annex II‚ page 17

).

Содержание MT 180

Страница 1: ...Installation and Maintenance Manual IM 1019 Group Fan Coil Part Number IM 1019 Date October 2011 2011 Daikin MT 180 Programmable Thermostat...

Страница 2: ...Program 10 System Check out 11 Condensate Overflow Interrupt 11 Thermostat configuration Service Menu 11 Technical and Application Notes 12 Fan Operation 12 Standard Fan Operation 12 Staged Fan Opera...

Страница 3: ...installing this control the Voltage Selection Switch must be placed in the correct position See instructions To avoid potential fire and or explosion do not use in potentially flammable or explosive...

Страница 4: ...n offers two different 7 Day Programmable Digital Heating Cooling Thermostat with constant fan or Fan cycled On Off Valve Control depending on the fan speed control used See Table 2 Table 2 Thermostat...

Страница 5: ...s for further information on Pipe Sensor Operation page 12 2 Pipe Operation Install JP4 The thermostat will per manently disable the Secondary Output and disables sys tem and fan invalid modes 4 Pipe...

Страница 6: ...off the entire system SETBACK Indicates the heating or cooling system is operating in setback mode Setback mode is an energy saving feature that can be either manually activated by the thermostat s u...

Страница 7: ...o the ther mostat s default display Up Down Arrow Button Operation The and buttons function in two ways When you are in the default display you can press to increase or to decrease the current tempera...

Страница 8: ...e factory default or installer selected during installation During setback mode when a demand for heating or cooling exists the fan will run at the lowest speed Automatic setback mode If your thermost...

Страница 9: ...ctory program meets your needs simply follow the Setting the Clock Day instructions and you re done If you want to change the preprogrammed times and or temperatures follow the instructions under Cust...

Страница 10: ...ect DAY Program the Evening period for SASU by repeating steps 1 through 8 but in Step 4 select EVE Program the Sleep period for SASU by repeating steps 1 through 8 but in Step 4 select SLEEP Now you...

Страница 11: ...terrupt The remote probe input can be used with a condensate overflow interrupt switch CO either in conjunction with a remote probe normally closed CO switch or with local sensing normally open CO swi...

Страница 12: ...a purge cycle if the sensed water temperature is ambiguous not adequately hot or cold The purge cycle algorithm can be either temperature or time based depending on the configuration of Service Menu...

Страница 13: ...stat outputs are disabled for 1 hour After 1 hour the purge cycle resumes at step 1 HVACSetback Systems Setback Operation Remove JP3 This is a low level input that is normally open When switch is clos...

Страница 14: ...trol of a guest room HVAC system It incorporates an innovative dual delay processor which allows the sensor to verify the nature of occupancies and is capable of eliminating unnecessary actuations of...

Страница 15: ...cy status detection If the sensor determines that a room is occupied it will allow normal HVAC control The sensor will wait for another door open signal before determining occupancy again In an unoccu...

Страница 16: ...d Start Time Heat Setpoint Temperature Cool Setpoint Temperature Monday Wake Day Evening Sleep Tuesday Wake Day Evening Sleep Wednesday Wake Day Evening Sleep Thursday Wake Day Evening Sleep Friday Wa...

Страница 17: ...urge Cycle 0 Time Based Default 1 Temperature Based Determines if the Purge Cycle will be Temperature or Time Based 17 Minimum Dead Band Adjustment 3 F Default 3 10 F 1 5 5 C A changeover deadband val...

Страница 18: ...Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty...

Отзывы: