ESIE19-06
|
Part 2. Troubleshooting
2.4. Component checklist
21/01/20
|
Version 1.1
Page 35
Modular L Smart
2.4.1.2. Damper motor + limit switch
Disconnected from main PCB
Part
Connector
Check
method
Reference (kΩ)
Remark
Measure point
motor
X22A, X28A
resistance
12,3
white wires
limit switch
X15A, X6A
resistance
∞
:
damper position
Hex. & Byp.
while damper moving contact
closed 0 Ω
Connected - main PCB power on
Part
Connector
Check
method
Reference
(Volt)
Remark
Measure point
motor
X22A, X28A
ACV
230
permanent when energized
limit switch
X15A, X6A
DCV
16
depends on position damper:
• at HEX & Bypass: 16 VDC
• during change: 0 VDC
Nȍ
0Ω
230V
230V
+ -
+ -