Part 2. Troubleshooting
2.3. Symptom based troubleshooting
21/01/20
|
Version 1.1
Page 31
Modular L Smart
2.3. Symptom based troubleshooting
2.3.1. Unit does not operate
2.3.2. Operation sometimes stops
Possible failures
Root cause
Check
Corrective action
Root cause category: component - electrical
Units do not operate.
Missing power supply to VAM
unit.
Check to make sure that the
rated voltage is supplied.
Restore the power supply.
Main PCB damaged (fuse
blown).
Check on main PCB:
• fuse,
• condition of varistors,
• jumper present on
connector X29A.
Arrange correct power supply
to VAM unit. Replace main
PCB if damaged component
found.
Root cause category: installation
On controller (BRC) no indica-
tion of operation mode HRV
(auto, heat exchanger or
bypass).
Initialisation not completed.
Check that at terminals P1P2
of VAM there is connection to
a remote controller (maybe in
group wiring, during installa-
tion cable forgotten).
Correct field wiring if no wiring
fount at terminals P1P2 of the
VAM unit.
Unit does not operate.
HRV unit no controller:
• no control “BRC…”,
• or no DCS… + group
number,
• or no external input closed
contact.
Check presence of central
control (DCS…) & group num-
bers are found.
Check presence of central
control (DCS…) & group num-
bers are found.
If no central control device
DCS…, connected wired con-
trol BRC… or external on/off
contact.
If only central control & no
indoor found, use wired control
BRC… to set each indoor
group number.
Root cause category: operating conditions
Units do not operate.
Unit operates out of the oper-
ating range.
Check the outdoor air temper-
ature.
Possible that some special
function stops intermediately
the unit:
• low outdoor air (cold region
operation),
• direct ducting,
• pre-cool/pre-heat function.
Possible failures
Root cause
Check
Corrective action
Root cause category: component - electrical
Operation sometimes stops.
A power failure of 2 to 10
cycles (of the power supply
sinus) can stop the VAM unit
operation (operation lamp off).
Check the power supply.
Restore the power supply.
Root cause category: operating conditions
Fan stops sometimes.
When the main PCB judges
that the damper needs to
change position, fan motors
will be stopped during the
change of the damper.
Check the operation of the
damper.
Check the temperature at the
outdoor air intake and indoor
air return side.
Содержание Modular L Smart
Страница 1: ...Service Manual Modular L Smart ESIE19 06 ...
Страница 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Страница 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Страница 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Страница 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...
Страница 62: ...ESIE19 06 Part 5 Appendix Page 62 21 01 20 Version 1 1 Modular L Smart This page is deliberately left blank ...
Страница 86: ...ESIE19 06 Part 5 Appendix 5 4 Switch box Modular L Smart Page 86 21 01 20 Version 1 1 Figure 5 23 Control PCB ...