![Daikin MKS-T Series Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/daikin/mks-t-series/mks-t-series_service-manual_3280982137.webp)
SiSG121917E
Troubleshooting for MSP Duct Type Indoor Unit
Part 6 Service Diagnosis
132
6.5 Drain System Abnormality
Error Code
AF
Method of Error
Detection
Water leakage is detected based on the float switch ON/OFF changeover while the compressor
is not operating.
Error Decision
Conditions
The float switch changes from ON to OFF while the compressor is OFF
Supposed
Causes
Error in the drain pipe installation
Defective float switch
Defective indoor unit PCB
Troubleshooting
YES
YES
N
O
N
O
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
The float s
w
itch may
b
e
defecti
v
e. Check if the
drain-
u
p height and the
horizontal pipe length
exceed the specifications.
Clogged
w
ater drain
system, clogged drain
p
u
mp, or fa
u
lty float s
w
itch
Replace the indoor
u
nit
PCB (control PCB). Check
if the drain-
u
p height and
the horizontal pipe length
exceed the specifications.
(R24692)
Are
the float s
w
itch and
the drain pipe
normal?
Is the
w
ater drain system
normal?
Содержание MKS-T Series
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B...