OM 1263 • MICROTECH UNIT CONTROLLER 20 www .DaikinApplied .com
View/Set Menu
Temperature Menu
Menus in the Temperatures menu contain unit temperature status information .
Table 4: Temperature Menu
Item Display Name
Default Setting
Range
Password Level
OA Temp=
—
-50 .0 – 200 .0°F
6
DRT1=
—
-50 .0 – 392 .0°F
6
DRT3=
—
-50 .0 – 392 .0°F
6
SRT=
—
-50 .0 – 200 .0°F
6
DFT=
—
-50 .0 – 200 .0°F
6
IRT=
—
-50 .0 – 150 .0°F
6
ORT=
—
-50 .0 – 150 .0°F
6
INVCompTemp=
—
-50 .0 – 392 .0°F
2
OA Temp
is a status only item which displays the current
temperature reading from the unit mounted outdoor air
temperature sensor .
DRT1
is a status only item which displays the current inverter
compressor discharge refrigerant line temperature sensor
reading .
DRT3
is a status only item which displays the current fixed
compressor (Comp 3) discharge refrigerant line temperature
sensor reading .
SRT
is a status only item which displays the current suction
refrigerant line temperature sensor reading .
DFT
(Heat Pump only) is a status only item which displays the
current defrost temperature sensor reading .
IRT
(Heat Pump only) is a status only item which displays the
current indoor refrigerant temperature sensor reading .
ORT
(Heat Pump only) is a status only item which displays the
current outdoor refrigerant temperature sensor reading .
INVCompTemp
(15 ton unit size only) is a status only
item which displays the current inverter compressor body
temperature sensor reading .
Flow Status Menu
Table 5: Flow Status Menu
Item Display
Name
Default Setting
Range
Password Level
Supply Fan=
—
Off
6
On
Ret/Exh Fan=
—
Off
6
On
Supply Fan
is a status only item that indicates the current S/S
state of the supply fan .
Ret/Exh Fan
is a status only item that indicates the current S/S
state of the exhaust or return fan .
RF/EF Control Menu
Table 6: Return/Exhaust Fan Speed Menu
Item Display
Name
Default Setting
Range
Password Level
RF/EF Cap=
—
0 – 100%
6
RF/EF Spd Cmd=
—
0 – 100%
6
RF/EF Cap
is a status only item which indicates the current
exhaust fan capacity .
RF/EF Spd Cmd
is an adjustable input to command the return/
exhaust fan speed .
SAF Spd Control Menu
Table 7: Supply Fan Speed Menu
Item Display
Name
Default Setting
Range
Password Level
SAF Speed=
—
0 – 100%
6
SAF Spd Cmd=
—
0 – 100%
6
SAF Speed
is a status only item that indicates the current
supply fan speed .
Speed Cmd
is a status only item that indicates the current
supply fan commanded speed .